2
Principles and conditions of modernization
Using multiple protocol detectors
10
Building Technologies
A6V10323158_d_en_--
Fire Safety
2015-04-09
2 Principles and conditions of modernization
2.1 Using multiple protocol detectors
Multiple protocol detectors of the Sinteso-S-LINE can quickly and efficiently take
the place of point detectors of other detector families which are already fitted.
The point detectors can either be replaced individually or as a complete detector
line.
Installed point detectors can be replaced e.g. during scheduled maintenance visits
by a service technician.
2.2 Characteristics of multiple protocol detectors
The multiple protocol detectors FDOOT241-x/-Ax may communicate via different
detector line protocols.
These detectors automatically recognize the protocol on the detector line (e.g.
FDnet or collective) and switch to this protocol.
This functionality simplifies detector line commissioning during modernization
because additional measures are not normally needed on the point detector.
The following detectors with ASAtechnology (S-LINE) are available when operating
on the FDnet:
Neural fire detector
FDOOT241-8
Neural fire detector
FDOOT241-9
Neural fire detector
FDOOT241-A3
Can be used addressed in MS8/PMT
mode
Can be used in collective mode
Can be used addressed in AnalogPLUS
mode
Can be used addressed in the FDnet
Neural fire detector
FDOOT241-A4
Neural fire detector
FDOOT241-A5
Neural fire detector
FDOOT241-A9
Can be used addressed in
SIGMALOOP mode
Can be used addressed in interactive
mode
Can be used in collective mode
Can be used addressed in the FDnet