Commissioning
Localization and device testing
6
48 | 62
Building Technologies
009757_f_en_--
Fire Safety
2016-08-23
6 Commissioning
The devices are commissioned via the control panel. The exact procedure is
described in the control panel documentation.
Conduct a performance check once commissioning is complete.
6.1 Localization and device testing
The manual call points have an internal alarm indicator. This internal alarm
indicator may also be activated from the control panel for localization and device
testing.
FDM221
The LED indicator of the alarm indicator has the following meanings:
LED indication
Meaning
Off
Normal condition
Green
Flashes once per second
Test mode is active
Red
Flashes once per second
Localization is active
o r
Alarm is triggered
Red and green alternating
Flashes twice per second
Alarm is triggered/localization is active
a n d
Test mode is active
FDM225, FDM226
The LED indicator of the alarm indicator has the following meanings:
LED indication
Meaning
Off
Normal condition
Red
Flashes brightly once per
second
Localization is active
o r
Alarm is triggered
Red
Flashes weakly twice per
second
Test mode is active
Red
Flashes twice per second,
alternately weakly and brightly
Alarm is triggered/localization is active
a n d
Test mode is active