Mounting / Installation
Installation
5
37 | 62
Building Technologies
009757_f_en_--
Fire Safety
2016-08-23
Manual call point FDM225 with back box
Observe the country-specific regulations for the exact installation height!
The manual call point FDM225 can be installed in a recessed box or with a back
box FDMH295-x (accessories).
If you are installing the manual call point in a recessed box, you can go directly to
the 'Installation [ 39]' chapter.
If you are installing the manual call point with a back box, proceed as follows:
The manual call point FDM225 is prepared for installation. See the chapter
1. Pull the cables through the entry opening(s) into the back box.
2. Secure the back box at a height of 0.9…1.6 m on an even surface.
The manual call point FDM225 is now prepared for electrical connection.
Figure 15: Installing the manual call point FDM225 with a back box FDMH295-x