Siemens Industry, Inc.
Building Technologies  Division

A6V11231630_en--_b

5

TO UPGRADE FROM

Follow the procedure below to upgrade an Cerberus PRO Modular panel from a

PMI TO FCM2041-U3

PMI to a FCM2041-U3.

1.

Please ensure you are using Zeus-C, 1.0 or greater.

2.

Create a new project in Zeus (

File>New

) to avoid overwriting a current

project.  The new project’s filename is not important.

3.

Download the current configuration from the PMI.
a) Connect the Laptop via the Upload cable and select

Build>Transfer>Configuration From Panel.

b) An .hrc configuration file from the PMI control panel downloads to the

Zeus host PC. Initially, the Zeus Transfer dialog will open, with settings for
serial port and transfer protocol. Once these are set, the Transfer Con-
figuration dialog will display information the PMI’s current configuration,
software and firmware versions. You can select the panel from which to
download (if there are multiple compiled configurations in the host PC),
and also choose to download the PMI’s current history file into the
project directory. Once you have begun the transfer, the Transfer
Progress dialog displays transfer progress and status messages, and
allows you to cancel the transfer.

4.

Once the panel configuration is downloaded, close the new project, use

Tools > Decompile

 to open the downloaded .hrc configuration file as a

project in Zeus.

5.

In the Zeus tool replace the PMI with the new FCM2041-U3.

Please make sure you are converting the correct PMI with a FCM2041-U3 by match-

ing the address of the switches on the back of the PMI.

a) In the configuration which you have just removed from the original PMI,

click on the PMI module in the physical tree. Select the Edit menu and
click on “

Find/Replace Tree  Node

”. A dialog box will open and allow you

to replace the PMI with the FCM2041-U3.

b) Once this is completed, save and then compile the configuration.

Remove ELECTRICAL POWER prior to removing the original PMI and installing the
new FCM2041-U3 in the enclosure.

c) Physically remove the original PMI and install the new FCM2041-U3 on

the inner door of the enclosure. (For more detail see the INSTALLATION
section and Figure 4 of this document.)

d) Re-attach the 60-pin cable to the connector at the top of the FCM2041-

U3 (see Figures 5 and 6) as well as any other original connections to the
PMI.

e) Apply power and allow the unit to initialize.

6.

Transfer the configuration to the Panel.
a) Connect the USB programming cable to the FCM2041-U3 USB type B

connector labeled “UPLOAD” at the bottom of the unit. (Refer to Figure
2.)

b)  In the Zeus configuration, select the module in the Physical Tree. Then

select 

Build>Transfer>Configuration to Panel

. An .hrc configuration file

uploads from the Zeus host PC to the FCM2041-U3 control panel,
overwriting the existing configuration in the panel.
i) Initially, the Zeus Transfer dialog will open, with settings for serial port

and transfer protocol. Once these settings are made, the Transfer

Содержание FCM2041-U3

Страница 1: ...2041 U3 contains a full VGA LCD Touch Screen and LEDs for displaying system status An audible sounds when there are unac knowledged events on the FCM2041 U3 The display is surrounded by keys that are used to control the displayed information and to navigate through these screens Keys are also provided to obtain help and to enter into the menu features of the FCM2041 U3 Refer to Figure 1 On the bac...

Страница 2: ... s e r d r a h r o f s d n o c e s 5 d l o H 2 1 D S I M P G e r o t s o t d e s u t r o p d r a c D S n o i t a m r o f n i p u k c a b d n a e s a b a t a d 2 D S I M P G w o l l a o t d e s u t r o p d r a c D S y t i l i b a p a c S U T A T S l a m r o n e t a c i d n i o t t h g i l s t n e m g e s g n i k l a W n a f i d e y a l p s i d s i e d o c r o r r E n o i t a r e p o d e t c e t e d...

Страница 3: ... t e N T E N X I M P n o g n i t t e S h c t i w s s n o i t p O 4 S n o g n i t t e s o N t i g i d o w t e h t o t s s e r d d a e d o n T E N X e h t t e S s u e Z n i t i r o f d e n g i s s a s s e r d d a s u e Z n i g n i t t e S m o r f s s e r d d a e d o n t i g i d o w t T E N X e h t t e S o t e r u s e B e e r t l a c i s y h p s u e Z e h t n i 4 6 1 0 s o r e z g n i d a e l t e s M...

Страница 4: ...vents are acknowledged a reset button becomes available in the lower right side of the display If notification appliances were active two additional buttons appear at the bottom of the screen These allow the operator to silence or unsilence the notification appliances When the notification appliances are silenced the Audibles Silenced LED lights The system can only be reset with the notification a...

Страница 5: ...s tool replace the PMI with the new FCM2041 U3 Please make sure you are converting the correct PMI with a FCM2041 U3 by match ing the address of the switches on the back of the PMI a In the configuration which you have just removed from the original PMI click on the PMI module in the physical tree Select the Edit menu and click on Find ReplaceTree Node A dialog box will open and allow you to repla...

Страница 6: ...sfer theTransfer Progress dialog displays transfer progress and status messages and allows you to cancel the transfer When you click OK at the transfer complete message the control panel will reset itself with the new configuration ELECTRICAL RATINGS r e w o P t u p n I r e w o P t u p t u O t n e r r u C e n a l P k c a B V 4 2 A m 5 9 1 d n a T E N X T E N H h c a E r i a P k r o w t e N N A C x...

Страница 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Страница 8: ...nc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V11231630_en _b This page has been left intentionally blank P N A5Q00075185 ...

Отзывы: