Siemens FCM2041-U3 Скачать руководство пользователя страница 4

Siemens Industry, Inc.
Building Technologies  Division

A6V11231630_en--_b

4

Figure 5

Connecting the FCM2041-U3 to the CC-5

Figure 6

Connecting the FCM2041-U3 to the RNI

Make sure that all cables snap fully into their connectors and close the locking levers
over the top of each cable connector. Secure the cable in the back box using cable
ties and the tie down points in the enclosure. The cable must have sufficient slack to
allow the inner door to open fully without putting stress on the cable.

OPERATION

In the normal standby condition the FCM2041-U3 displays the site specific custom
message, the time and date, and a synopsis of the system status.

When an event occurs in the system, the display enters the Alert mode. The event is
displayed, the local audible sounds and the tab on the display for the corresponding
event queue flashes. If the event type is Alarm, Trouble, or Supervisory, the appropriate
LED blinks. If the event caused notification appliances to sound the Audibles On
indicator lights. At the bottom of the screen an acknowledge button is displayed.
Pressing this button acknowledges the event and silences the local audible. Once all
events are acknowledged a reset button becomes available in the lower right side of
the display. If notification appliances were active, two additional buttons appear at the
bottom of the screen. These allow the operator to silence or unsilence the notification
appliances. When the notification appliances are silenced the Audibles Silenced LED
lights. The system can only be reset with the notification appliances silenced.

If more events are present in the system than can be displayed on a single screen a
scroll bar appears to the right of the event list. Pressing the up and down navigation
buttons to the right of the LCD allows the operator to move through the list. The
selected event is highlighted in the display. Pressing the More Info button will display
a screen showing details relating to the selected event. Other buttons also appear at
the bottom of this screen. There is an expanded text message available and a
selection to show all of the devices associated with the event that are active. The
operator can return to the previous screen by pressing the ESC button. (For more
detail on FCM2041-U3 operation, refer to the Cerberus PRO Modular Manual,
Document ID A6V11231627.)

If the LED under one of the 

 

 buttons above the LCD is lit, pressing the

button moves the highlight to the next queue. Use the 

 

 buttons to shift to

the first or last queue.

Содержание FCM2041-U3

Страница 1: ...2041 U3 contains a full VGA LCD Touch Screen and LEDs for displaying system status An audible sounds when there are unac knowledged events on the FCM2041 U3 The display is surrounded by keys that are used to control the displayed information and to navigate through these screens Keys are also provided to obtain help and to enter into the menu features of the FCM2041 U3 Refer to Figure 1 On the bac...

Страница 2: ... s e r d r a h r o f s d n o c e s 5 d l o H 2 1 D S I M P G e r o t s o t d e s u t r o p d r a c D S n o i t a m r o f n i p u k c a b d n a e s a b a t a d 2 D S I M P G w o l l a o t d e s u t r o p d r a c D S y t i l i b a p a c S U T A T S l a m r o n e t a c i d n i o t t h g i l s t n e m g e s g n i k l a W n a f i d e y a l p s i d s i e d o c r o r r E n o i t a r e p o d e t c e t e d...

Страница 3: ... t e N T E N X I M P n o g n i t t e S h c t i w s s n o i t p O 4 S n o g n i t t e s o N t i g i d o w t e h t o t s s e r d d a e d o n T E N X e h t t e S s u e Z n i t i r o f d e n g i s s a s s e r d d a s u e Z n i g n i t t e S m o r f s s e r d d a e d o n t i g i d o w t T E N X e h t t e S o t e r u s e B e e r t l a c i s y h p s u e Z e h t n i 4 6 1 0 s o r e z g n i d a e l t e s M...

Страница 4: ...vents are acknowledged a reset button becomes available in the lower right side of the display If notification appliances were active two additional buttons appear at the bottom of the screen These allow the operator to silence or unsilence the notification appliances When the notification appliances are silenced the Audibles Silenced LED lights The system can only be reset with the notification a...

Страница 5: ...s tool replace the PMI with the new FCM2041 U3 Please make sure you are converting the correct PMI with a FCM2041 U3 by match ing the address of the switches on the back of the PMI a In the configuration which you have just removed from the original PMI click on the PMI module in the physical tree Select the Edit menu and click on Find ReplaceTree Node A dialog box will open and allow you to repla...

Страница 6: ...sfer theTransfer Progress dialog displays transfer progress and status messages and allows you to cancel the transfer When you click OK at the transfer complete message the control panel will reset itself with the new configuration ELECTRICAL RATINGS r e w o P t u p n I r e w o P t u p t u O t n e r r u C e n a l P k c a B V 4 2 A m 5 9 1 d n a T E N X T E N H h c a E r i a P k r o w t e N N A C x...

Страница 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Страница 8: ...nc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada Document ID A6V11231630_en _b This page has been left intentionally blank P N A5Q00075185 ...

Отзывы: