LED module and LED module (red/yellow, yellow)
2
Adjustment elements
15
Siemens Industry, Inc.
A6V10315030_b_en_--
Building Technologies Division
2013-06-04
Element
Des.
Function
Indicators
H301…H371 LEDs for indication on front (designation on PCB)
Switch
S15
Switch for device address
Connections
X400
Peripheral data bus connection (input)
X402
Peripheral data bus connection (output)
X407
Not used
X409
Not used
2.3
Adjustment elements
Switches 1…4 (S15) are used to assign an address to the LED indicator. Switches 5
and 6 (S15) can each be used to run an LED test.
Switch S15
Address
1
1
2
3
4
5
6
20
ON
21
ON
22
ON
ON
23
ON
24
ON
ON
25
ON
ON
26
ON
ON
ON
27
ON
28
ON
ON
29
ON
ON
30
ON
ON
ON
31
ON
ON
32
ON
ON
ON
33
ON
ON
ON
34
ON
ON
ON
ON
35
ON
LED test red
ON
LED test yellow
Empty fields = switch in 'OFF' position
1
Address, which has to be entered in the Engineering tool set in the 'Address' field for
the appropriate switch position.
firealarmresources.com