Siemens Industry, Inc
,
A6V10334254_en--_g
Building Technologies Division
7
INSTALLATION ON XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO
MODULAR
For instructions on installing and wiring the FCA2015-U1 DACT to the XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular panel, refer to the XDACT-ASSY Installation Instructions, Document ID
A6V10807278.
If a message indicating an XDACT firmware mismatch is displayed on the Operator Interface (OI), upgrade
the XDACT firmware as follows.
FIRMWARE UPDATE ON XLS/DESIGO FIRE SAFETY MODULAR/CERBERUS PRO
MODULAR SYSTEMS
To update the firmware on an FCA2015-U1 that is installed on a XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular system, establish an Ethernet connection between the PC and the OI, then select the XDACT
module in the Zeus configuration. Next, select
Build > Transfer > Module Firmware To Panel…
in Zeus.
Select the XDACT firmware file under
Firmware File
, then set the Connection Settings as needed and click
Start Transfer
to begin the update.
Transfer Completed
will be displayed in Zeus after the firmware update
has completed.
FCA2015-U1 WIRING
NOTE:
The RJ31X provides a convenient connection allowing the DACT to be installed and removed
without requiring re-wiring and can be installed by the telephone installer.
NOTE:
If installed in Canada, the signal receiving centre must not share a common communication channel
with the protected premises. A dedicated line must be installed for use only by the FCA2015-U1.
NOTE:
Either of the two lines at X300 or X301 can be disabled using the Engineering Configuration tool for
the case where the dialer is connected to an alarm communicator that is capable of transmitting with
two separate technologies (ex. GSM and POTS). Consult the installation instructions for the
communicator to determine if it supports this capability.