Siemens Industry, Inc
,
A6V10334254_en--_g
Building Technologies Division
6
OVERVIEW
The FCA2015-U1 Digital Alarm Communicator Transmitter (DACT) Board is an optional module for the
Desigo FC2025/2050, FV2025/2050, Cerberus PRO FC922/924, FV922/924, and XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular Fire Alarm System Control Panels. The DACT provides telephone line
connections for communication with a DACR (Digital Alarm Communicator Receiver). The DACT Board is
mounted inside the Fire Alarm cabinet. The DACT Board options are set through the control panel
programming sequence.
INSTALLATION ON DESIGO AND CERBERUS PRO PANELS
Dialer FCA2015-U1 mounted on 2HU Enclosure
Dialer FCA2015-U1 mounted on the back of the inner
door (when used with a 3HU Enclosure)
Step 1)
Installation should be performed by
qualified personnel who have
thoroughly read and understood this
instruction sheet.
Step 2)
Disconnect BATTERY and AC on the
cabinet prior to working on the
equipment.
Step 3)
Mount FCA2015-U1 as shown using
the four screws that are supplied.
Step 4)
Attach conduit and run wires as
required. Wire Size: 12-22AWG
Step 5)
Connect the Serial Communication
Cable to the fire system control unit as
required.
Step 6)
Apply power to system.
Step 7)
Program for proper operation.
NOTE
: See the Desigo FC2025/2050,
FV2025/2050 Configuration manual,
Document ID A6V10315023, and
Cerberus PRO FC922/924, FV922/924
Fire Detection System Configuration
manual, Document ID A6V10333423, for
details on programming.
Step 8)
Check for proper operation.
PARTS SUPPLIED
1
DACT Board
4
Screws
1
Instruction Sheet
1 Serial Communication Cable
*4 1 ¾” x ¼” Hex Male to Female
Standoff
*Used for FCM2019-U2/-U3 or FCM2035-
U2/-U3 only.
DIALER
FCA2015
PMI
OPERATING UNIT