OVERVIEW 

 
The FCA2015-U1 Digital Alarm Communicator Transmitter (DACT) Board is an optional module for the 
Desigo FC2025/2050, FV2025/2050, Cerberus PRO FC922/924, FV922/924, and XLS/Desigo Fire Safety 
Modular/Cerberus PRO Modular Fire Alarm System Control Panels. The DACT provides telephone line 
connections for communication with a DACR (Digital Alarm Communicator Receiver). The DACT Board is 
mounted inside the Fire Alarm cabinet. The DACT Board options are set through the control panel 
programming sequence. 

 

 

INSTALLATION ON DESIGO AND CERBERUS PRO PANELS 

 
Dialer FCA2015-U1 mounted on 2HU Enclosure 

 

 
Dialer FCA2015-U1 mounted on the back of the inner 
door (when used with a 3HU Enclosure) 
 

 

Step 1) 

Installation should be performed by 
qualified personnel who have 
thoroughly read and understood this 
instruction sheet.  

Step 2) 

Disconnect BATTERY and AC on the 
cabinet prior to working on the 
equipment.  

Step 3) 

Mount FCA2015-U1 as shown using 
the four screws that are supplied.    

Step 4) 

Attach conduit and run wires as 
required. Wire  Size: 12-22AWG 

Step 5) 

Connect the Serial Communication 
Cable to the fire system control unit as 
required.  

Step 6) 

Apply power to system.  

Step 7) 

Program for proper operation. 

NOTE

:  See the Desigo FC2025/2050, 

FV2025/2050 Configuration manual, 
Document ID A6V10315023, and 
Cerberus PRO FC922/924, FV922/924 
Fire Detection System Configuration 
manual, Document ID A6V10333423, for 
details on programming. 

Step 8) 

Check for proper operation. 
 
 
 
 

PARTS SUPPLIED 

DACT Board 

Screws 

Instruction Sheet 

1   Serial Communication Cable 
*4   1 ¾”  x ¼” Hex Male to Female 
Standoff 

 
 

*Used for FCM2019-U2/-U3 or FCM2035-
U2/-U3 only. 

DIALER
FCA2015

PMI

OPERATING UNIT

Содержание FCA2015-U1

Страница 1: ...Siemens Industry Inc Building Technologies Division FCA2015 U1 Serial Digital Alarm Communicator Transmitter DACT Installation Instruction ...

Страница 2: ...ent as well as utilization of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www ...

Страница 3: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Страница 4: ...ERBERUS PRO PANELS 6 INSTALLATION ON XLS DESIGO FIRE SAFETY MODULAR CERBERUS PRO MODULAR 7 FIRMWARE UPDATE ON XLS DESIGO FIRE SAFETY MODULAR CERBERUS PRO MODULAR SYSTEMS 7 FCA2015 U1 WIRING 7 FCA2015 U1 FORMAT DESCRIPTION 8 COMPATIBLE RECEIVERS FORMATS 8 COMPATIBLE ALARM COMMUNICATORS 8 FCA2015 U1 EVENT CODES 10 FCC Statement 12 ...

Страница 5: ... the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems UL 864 certain programming features or options must be limited to specific values or not used at all as indicated below Program feature or option Permitted in UL 864 Y N Possible settings Settings permitted in UL 864 PERIODIC TEST PROGRAMMING RANGE Y 1 24 Hours 1 6 Hours Digital Communication format Y SIA DC...

Страница 6: ...tep 1 Installation should be performed by qualified personnel who have thoroughly read and understood this instruction sheet Step 2 Disconnect BATTERY and AC on the cabinet prior to working on the equipment Step 3 Mount FCA2015 U1 as shown using the four screws that are supplied Step 4 Attach conduit and run wires as required Wire Size 12 22AWG Step 5 Connect the Serial Communication Cable to the ...

Страница 7: ...ld Transfer Module Firmware To Panel in Zeus Select the XDACT firmware file under Firmware File then set the Connection Settings as needed and click Start Transfer to begin the update Transfer Completed will be displayed in Zeus after the firmware update has completed FCA2015 U1 WIRING NOTE The RJ31X provides a convenient connection allowing the DACT to be installed and removed without requiring r...

Страница 8: ...digit code up to four rounds at 20 pps with 1400 Hz handshake frequency 4 2 2300HZ Sends a 4 digit account number and a 2 digit code up to four rounds at 20 pps with 2300 Hz handshake frequency COMPATIBLE RECEIVERS FORMATS Receiver Manufacturer Compatible Receivers SIA DCS 8 SIA DCS 20 Ademco Contact ID 3 1 1400HZ 3 1 2300HZ 4 2 1400HZ 4 2 2300HZ Honeywell M8000 SIA DCS 8 SIA20 Ademco Contact ID S...

Страница 9: ... shall be within 20 feet and in conduit All compatible Alarm Communicators shall be installed in accordance with their installation instructions A means must be provided for detection of faults on the communicator by the fire alarm panel as described in the installation instructions for the communicator This is typically done by connecting a trouble activated relay on the communicator to an input ...

Страница 10: ...e Line 2 Trouble Restore LR 2 3 352 00 000 7 72 Data Lost RT 0 1 354 00 000 8 88 Automatic Test Normal RP 1 602 00 000 9 30 Automatic Test Off Normal RY 1 608 00 000 9 39 Manual Test RX 0 1 601 00 000 9 99 Test Activation FX pppp 1 611 0p ppp 9 91 Gas Alarm GA pppp 1 151 0p ppp 0 03 Gas Alarm Restore GH pppp 3 151 0p ppp 2 23 Communications Fail YC 1 350 00 000 8 84 System Reset OR 0 1 305 00 000 ...

Страница 11: ...S and Ademco Contact ID can be used for UL 864 10 th Edition off premises signaling ELECTRICAL RATINGS Standby 24DC Module Current 33 5mA Active 24VDC Module Current 43 5mA INDICATORS LED Function Description H100 OK LED Hardware is functionally good H200 L1 FLT Red LED on Solid Line Connection error while dialing out Line 1 Red LED Flashing DACT Dialing out on Line 1 H201 L2 FLT Red LED on Solid ...

Страница 12: ...with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the in...

Отзывы: