E3C011 Battery charging module
24
Siemens Building Technologies
007831_a_en_--.doc
Fire & Security Products
03.2004
7.4 Important
components
E3C011
F501
F502
F503
ca.28
ON
S3
S2
ON
ST1
S1
1
1
K1
1
4
Fuses
F501 6.3A/T* battery "Positive"
F502 6.3A/T* battery "Negative"
F503 6.3A/T* Battery "Centre"
* Fuse with high breaking capacity (sand-filled)
Key "S1": System start only with
battery (without mains voltage)
Flat cable header "ST1" (26-pin): I-Bus
Plug-in terminals "K1":
Supply for the modules "I-Bus"
LED indicator block "Power supply status"
(see table LED indicator block)
Programming switch "S2": Set battery type
Programming switch "S3": Set "I-Bus address"
µ
P
ASIC
I-Bus
(see chapter ‘Programming switches’)
(see chapter ‘Programming switches’)
7.5 Programming
switch
”S2”
To set temperature compensation according to information from the various battery
manufacturers
Possible battery variants
Programming switch S2
Var.
Battery
manufacturer
Battery
model
S2-1 S2-2 S2-3 S2-4
0
off off off off
1
on
off off off
2 Varta
Shin-Kobe (Hitachi)
Kobe PSD (Power Storage Germany)
CF 12-24 (VM 1224)
HP..-12
HP..-12
off
on
off off
3 Genesis
G12V120W15
on
on
off off
4 Sunrise
Panasonic
LCL 12V24S
LCL 12V..P
off off
on
off
5
Phoenix (Korea)
FNC 12..0
on
off
on
off
6 Yuasa
NP..-12B
off
on
on
off
7 Sonnenschein
Dryfit
A212/..G5
on
on
on
off
8 Power-Sonic
PS12..0
off off off
on
9 Hagen
Drysafe
HDS-12..0NB
on
off off
on
10 Sonnenschein
Dryfit
A512/..G5
off
on
off
on
11 ALARMCOM
(FIAMM)
FG...
on
on
off
on
12
off off
on
on
13
on
off
on
on
14
off
on
on
on
15
on
on
on
on
”S2” is set to variant 11 (ALARMCOM) at the factory
Floating charge voltage as a function of temperature, or for diagrams of the various types of battery
see page 25