Communication Protocol
MicroHarmony Cell Sizes 40 - 260A Manual
11-6
19001467: Version 1.0
s
11
11.8 Mode 01 Data
11.8.1 Modulator to CCB
Mode 01 is dedicated for collecting diagnostic information from the CCB and is also used for issuing ‘Cell Fault
Reset’ commands by setting bit 2 high (‘1’).
Table 11-7: Mode 01 Modulator to CCB Data
11.8.2 CCB to Modulator
The response data for Mode 01 is shown below, where bit 2 indicates a fault when set high (‘1’) and bits 3-6 indicate
a fault when set low (‘0’).
Table 11-8: Mode 01 Data from CCB to Modulator
Bit
Description
0
1 -> Mode definition bit
1
0 -> Mode definition bit 1
2
Cell Fault Reset
3
0 (not used)
4
0 (not used)
5
0 (not used)
6
Sync pulse for temperature engine
7
Odd Parity Bit
Bit
Description
0
1 -> Mode definition bit 0
1
0 -> Mode definition bit 1
2
Any Device Out of Saturation (OOS) Fault (Q1,Q2,Q3, or Q4)
3
Not Cell DC Bus Overvoltage
4
Not Cell DC Bus Undervoltage
5
Not Cell Capacitor Sharing Fault
6
Not Communication Fault detected by CCB
7
Odd Parity Bit
Содержание Eupec
Страница 10: ...Safety Precautions and Warnings MicroHarmony Cell Sizes 40 260A Manual viii 19001467 Version 1 0 s ...
Страница 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Страница 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Страница 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Страница 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Страница 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Страница 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Страница 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Страница 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Страница 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Страница 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...