Cell Control Board - 10000432
MicroHarmony Cell Sizes 40 - 260A Manual
5-6
19001467: Version 1.0
s
5
Notes:
1.
These conditions generate a Cell Fault which disables all output IGBTs and is annunciated by Down Bit 2 in
Mode 00
2.
These conditions do not generate a Cell Fault and can only be monitored by Down Bit packet in Mode 00
3.
These conditions can only be monitored in the Non Run Mode 11 and are for cell diagnostic purposes only.
5.6 Communication
The cell control board communicates to the Perfect Harmony control system via a duplex fiber optic cable on a
proprietary communication protocol. See Chapter 11,
Communication Protocol
, for details.
∇
∇
∇
Communication
Fault
1
CMFLT
This is complimentary meaning of LINK ON, which is displayed on CCB
by means of LED lamp. Therefore, if LINK ON is off then CMFLT is
active. CMFLT becomes active after either parity error occurred or QValid
from EPLD is not active. CMFLT is active low.
Cell Protection
CCB Board
Ref. Signal
Description and Thresholds
Содержание Eupec
Страница 10: ...Safety Precautions and Warnings MicroHarmony Cell Sizes 40 260A Manual viii 19001467 Version 1 0 s ...
Страница 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Страница 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Страница 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Страница 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Страница 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Страница 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Страница 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Страница 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Страница 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Страница 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...