Diagnostic messages
A
A.1
Diagnostics alarms
Diagnostic messages
For each diagnostic event, a diagnostic message is output and the ER LED flashes on the module.
The diagnostic messages can, for example, be read from the diagnostic buffer of the CPU.
There can be more than one diagnostics alarm at the same time.
Table A-1
Diagnostic messages, their meaning and possible remedies
Diagnostics mes‐
sage
Channel
error
type
(CET)
Exten‐
ded chan‐
nel error
type
(CET)
Assignment Meaning
Remedy
Configuration error:
Station Stop – No
server module
0x0602
0x0693
Configura‐
tion
No server module was
present during power-up of
an ET 200SP HA station.
Verify that the server module is
correctly installed in the rack.
Configuration error:
Module parameter
<potential group> er‐
rors or incorrect ter‐
minal block present
in real slot <slot>
0x0602
0x0691
Configura‐
tion
The installed terminal block
does not match the configu‐
ration.
Ensure that a matching termi‐
nal block is installed.
Configuration error:
Permissible back‐
plane bus size excee‐
ded
0x0602
0x0698
Configura‐
tion
The total width of the instal‐
led modules exceeds the per‐
missible assembly length of
1300 mm.
Verify that the backplane bus
configuration does not exceed
the permissible size.
The server module must be the
last module plugged in (high‐
est permissible slot number:
58).
Configuration error:
Incorrect backplane
bus configuration in
slot <slot>
0x0602
0x0699
Configura‐
tion
The maximum current de‐
mand of all plugged-in mod‐
ules exceeds 2100 mA.
The accompanying <slot> val‐
ue indicates the slot causing
the error.
Check the configuration of the
ET 200SP HA.
Configuration error:
Impermissible bus
adapter on interface
module
0x0602
0x069C
Configura‐
tion
The installed bus adapter
does not match the configu‐
ration.
Verify that a matching bus
adapter is installed.
Configuration error:
No server module
0x0602
0x069E
Configura‐
tion
The server module is pulled
during operation of an
ET 200SP HA station.
Ensure that the server module
is correctly installed in the rack.
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
45
Содержание ET 200SP HA
Страница 6: ...Security information IM 155 6 PN HA 6 Equipment Manual 09 2021 A5E39262148 AE ...
Страница 8: ...Preface IM 155 6 PN HA 8 Equipment Manual 09 2021 A5E39262148 AE ...
Страница 24: ...Parameters IM 155 6 PN HA 24 Equipment Manual 09 2021 A5E39262148 AE ...
Страница 26: ...Behavior of the device name IM 155 6 PN HA 26 Equipment Manual 09 2021 A5E39262148 AE ...