Article number
6DL1155-6AU00-0PM0
• ERROR LED
Yes; red LED
• MAINT LED
Yes; Yellow LED
• ACT LED
Yes; green LED
• Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
• Connection display LINK TX/RX
Yes; 2x green link LEDs on BusAdapter
Potential separation
between PROFINET and all other circuits
Yes; 1 500 V AC
between supply and all other circuits
Yes; Type tested with 1 500 V DC
Permissible potential difference
between different circuits
Safety extra low voltage SELV
Isolation
Isolation tested with
1 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
• horizontal installation, min.
-40 °C
• horizontal installation, max.
70 °C
• vertical installation, min.
-40 °C
• vertical installation, max.
60 °C
Dimensions
Width
50 mm
Height
138 mm
Depth
89 mm
Weights
Weight, approx.
192 g; without BusAdapter
Technical specifications
8.1 Technical specifications
IM 155-6 PN HA
Equipment Manual, 09/2021, A5E39262148-AE
37