Service
492
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
11.2
Checks and System Display
The single system elements carry out checks of the hardware and software. If an error is de-
tected, this leads
•
to a signaling on the LED display
•
dependent of the severeness of the error possibly
─
to an abort of the startup
─
in operation to a shutdown of the modules or firmware
After an errorless startup of a system element further checks are carried out.
11.2.1 Checks during Startup
Startup (step)
RY
ER
Error/reaction
Power-up or reset
™
˜
Start startup
™
•
Module defective
•
Massive error in the program memory
Check of the code memory (flash
PROM)
™
˜
PROM error (code)
•
Module is shut down
•
Startup is aborted
Check of the data memory (RAM) with
address error check
™
˜
RAM error (data)
•
Module is shut down
•
Startup is aborted
Check whether SD card is present
™
˜
SD card not present
Check of the checksum of all parame-
ter files and firmware files on the SD
card
™
˜
Checksum error on the SD card
•
Diagnosis information is set
Check whether all parameters on the
SD card are present
™
˜
Parameter files incomplete
•
Firmware is shut down
•
Startup is aborted
Check whether all firmware files on the
SD card are present
™
˜
Firmware code incomplete
Check whether the firmware code of
the subordinate system elements
(protocol elements, I/O Master Module)
is current
™
˜
If not,
at a later time
Revision check of the parameters in
the parameter memory
™
˜
If the parameters are not current, they are
loaded from the SD card
Check parameter memory (flash-
PROM)
™
˜
Checksum error of the parameters
•
Firmware is shut down
•
startup is aborted
Initiate the startup of the subordinate
system elements
™
˜
Check for accordance of the parame-
terized HW configuration with the
mechanical configuration (I/O Modules)
™
˜
Configuration error
•
the wrongly configured or defective module
is not operational
•
successional modules are not operational
Check of the configuration for pulse
command output
™
˜
Configuration error
•
Pulse command output is locked for all
modules
Содержание CP-8000
Страница 10: ...Open Source Software 10 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 74: ...Function Packages 74 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 468: ...Engineering via SICAM WEB 468 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 524: ...Service 524 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 556: ...Error Handling 556 Unrestricted SICAM A8000 CP 8000 CP 8021 CP 8022 Manual DC8 037 2 02 Edition 10 2017 ...
Страница 603: ...Use Cases SICAM A8000 CP 8000 CP 8021 CP 8022 Manual Unrestricted 603 DC8 037 2 02 Edition 10 2017 ...
Страница 604: ......