Issue 03/01
10 Engineering Information
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
139
Example
2
Using OFF3 instead of OFF1.
Set P0701 = 99 to enable BiCo function.
Set P0840 = 722.0 (On right via digital input 1).
Set P0848 = 722.0 (OFF3 via digital input 1).
Now the inverter will ramp between set points using the normal ramp time as set in
P1120 and 1121. However, at switch off from digital input 1, the inverter will turn off
with an OFF3, using the ramp rate set in P1135, which may be different to P1121.
An additional advantage is that the OFF3 function usually requires a second digital
input; here the BiCo function permits digital input 1 to perform a run right and an
OFF3.
Example
3
Selecting an alternative ramp time when a certain fixed frequency is selected.
Three fixed frequencies are selected using three digital inputs.
The digital inputs also select ‘on right’.
The third digital input also selects the alternative (Jog) ramp times.
NOTE:
This will only enable an alternative ramp up time, because, when digital input 3 is
switched low it will also de-select the alternative ramp time. Normal ramp down
time will therefore be used.
Step
Definition
Action
Result
1
Use fixed frequencies.
P1000 = 3
2
Enable BiCo functionality.
P0701 = 99
P0702 = 99
P0703 = 99
3
Define source of Fixed
Frequencies.
P1020 = 722.1
P1021 = 722.2
P1022 = 722.3
Defines the source of each fixed
frequency as digital input 1, 2, and 3.
4
Define mode of operation.
P1016 = 2
P1017 = 2
P1018 = 2
Sets the mode of operation of fixed
frequencies to “select fixed frequency and
on right command”.
5
Select Jog ramp times
instead of normal ramp
times.
P1124 = 722.2
Enables digital input 3.
NOTE:
Steps 3 and 4 use BiCo functions to set digital input 1 and 2. This function can also
be set using normal parameterization in Level 2.
Содержание COMBIMASTER 411
Страница 40: ...2 Installation Issue 03 01 MICROMASTER 411 COMBIMASTER 411 Operating Instructions 40 6SE6400 5CA00 0BP0 ...
Страница 60: ...3 Commissioning Issue 03 01 MICROMASTER 411 COMBIMASTER 411 Operating Instructions 60 6SE6400 5CA00 0BP0 ...
Страница 92: ...6 Troubleshooting Issue 03 01 MICROMASTER 411 COMBIMASTER 411 Operating Instructions 92 6SE6400 5CA00 0BP0 ...
Страница 98: ...7 Specifications Issue 03 01 MICROMASTER 411 COMBIMASTER 411 Operating Instructions 98 6SE6400 5CA00 0BP0 ...
Страница 102: ...8 Options Issue 03 01 MICROMASTER 411 COMBIMASTER 411 Operating Instructions 102 6SE6400 5CA00 0BP0 8 4 PROFIBUS Module ...
Страница 103: ...Issue 03 01 8 Options MICROMASTER 411 COMBIMASTER 411 Operating Instructions 6SE6400 5CA00 0BP0 103 8 5 EM Brake Module ...
Страница 154: ......
Страница 162: ...MICROMASTER 411 COMBIMASTER 411 Operating Instructions 162 6SE6400 5CA00 0BP0 ...
Страница 163: ...Issue 03 01 Geräteansicht MICROMASTER 411 COMBIMASTER 411 Operating Instructions 6SE6400 5CA00 0BP0 163 ...