4
Siemens
A6V11681604_enUS_b
Smart Infrastructure
2022-05-25
Status
Free Cooling LED Sensor LED
DAC LED
Humidity sensor error
-
Yellow On
-
CO
2
sensor error
-
LED Off
-
Air temperature failure/fault
-
Red On
-
Excess outdoor air
-
Red Blinking
-
Damper working ok
-
-
Green On
Damper stalled
-
-
Red On
Damper slippage
-
-
Red Blinking
Actuator alarm is reported
-
-
Fast Red Blinking
Terminal ACT-FB is configured
but no available feedback
signal (under-range or over-
range)
-
-
LED Off
NOTICE
If different faulty events occur at the same time, sensor/DAC LED lights up following the
priority below: Red (Fast Blinking) -> Red (On, Steady) -> Red (Blinking) -> Yellow -> Off ->
Green. For example, if there is a humidity sensor error and air temperature failure at the
same time, the sensor LED turns red rather than yellow.
After the Economizer controller enters the running state, it may take one minute for
peripheral devices to complete initialization. Before that, LED indication might be unstable.
Type Summary
Type
Order number
Description
POL224.00
S55392-C202-A100
POL224.00 Title24 Economizer Controller
POL224.05
S55392-C203-A100
POL224.05 Title24 Econ Cont, no housing
Order and Delivery
When ordering, provide both name and type reference, e.g. Economizer Controller,
POL224.00.