b. Wire normally de-energized devices (extinguishing smoke removal fan,
etc.) to the NO contacts between terminals 10 and 11 in order to acti-
vate these devices on alarm.
NOTE:
Relay contacts may not be in supervisory condition when
shipped.
INSTALLATION OF SMOKE DETECTORS
CAUTION:
Air Duct Detector Models AD-3XRI/3XRILP are designed
only for those detectors shown in the Smoke Detector
Compatibility section (See Tables 1and 2). Do not use any
other detector (See Figure 3,items 14, 15 and 21).
Programming
DI-BX, DI-BX3H Detectors
Model AD-3XRI, using X Series smoke detectors, can be programmed to
respond at a specific and unique address (See Figure 8). Program each
detector by referring to the table and notes in Figure 8. Record each
device number and zone in the space provided on the detector cover.
ID-60IB, ID-60IBH, ILI-1B, ILI-1BH, ILP-1 Detectors
Model AD-3XRI/3XRILP, using ID-60IB, ID-60IBH, ILI-1B, ILI-1BH, or ILP-1
detectors, can be programmed to respond at a specific and unique system
4
3
2
1
5
5
6
7
8
9
10 11
5
5
6
7
8
9
10 11
SEE NOTE 3
SEE NOTE 3
SEE NOTE 3
Model AD-3I or AD-3ILP
Model AD-3XRI or AD-3XRILP
Model AD-3XRI or AD-3XRILP
NOT
USED
TERMINAL
BLOCK
RED
BLACK
WIRE NUT
REQUIRED
NOT USED
NOT USED
RELAY
BOARD
ALARM CONTACTS
125 VAC/24 VDC, 3A
SEE NOTES 1 AND 2
ALARM CONTACTS
125 VAC/24 VDC, 3A
SEE NOTES 1 AND 2
TO NEXT
ADDRESSABLE
DEVICE
OPTIONAL
REMOTE ALARM
INDICATOR
MODEL RLX-1
OR RLX-2
ZONE WIRES FROM SIEMENS
BUILDING TECHNOLOGIES, INC.
SYSTEM XL3 CONTROL PANEL
+
+
+
+ +
+
+
+ _
_
-
-
-
_
-
NOTES:
1. The relay contacts are shown just after a reset pulse, which
represents the non-alarm condition.
2. If the relay contacts are being used to control 120 VAC operated
equipment, ensure that the conduit is properly attached to the internal
ground strap, using the proper conduit locking nuts.
Failure to
provide proper grounding may result in fatal electrical shock and
causes non-conformance with national and local codes.
3. Use DI-BX3, DI-BX3H, ID-60IB, ID-60IBH, ILI-1B, ILI-1BH, and ILP-1
detectors only.
Figure 6
Typical Connections for Models AD-3XRI and AD-3XRILP when used with XL3