![Siemens CEREBRUS PYROTRONICS AD-3XRI Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/siemens/cerebrus-pyrotronics-ad-3xri/cerebrus-pyrotronics-ad-3xri_installation-wiring-instructions_383332012.webp)
The cleaning and test program is recommended for 6 month intervals, or
more frequently, if needed, depending on the individual detector environment.
CAUTION:
Under no circumstances is the ionization or potoelectric
detector portion of the unit to be disassembled by anyone
other than an authorized Siemens Building Technologies,
Inc. Systems Technician. For service, contact your nearest
authorized Siemens Building Technologies, Inc. Service
Representative.
Periodic Testing
The unit should be tested periodically to ensure optimum performance.
This can be done by removing the sealing plug from the inlet sampling
tube on the opposite side of the duct and blowing smoke directly into the
inlet tube. Check that the fire alarm system is activated.
CAUTION:
If the fire alarm system is connected to a central station or
fire department, or has external devices such as fans,
extinguishers, etc., connected, notify appropriate personnel
and disconnect the external devices until all tests are
completed. After testing, reset the system, reconnect the
devices, and notify the personnel that the system is operat-
ing again.
The detector model number is the compatibility identifier.
COMPATIBLE CONTROL EQUIPMENT
Equipment
Installation/Wiring
Compatibility Identifier
Instructions
MXL
P/N 575-295370-2
XL3
P/N 315-183000-17
IXL (ICON-1)
P/N 315-092371-5
P/N 315-093235-5