Siemens CEREBRUS PYROTRONICS AD-3XRI Скачать руководство пользователя страница 10

10

4

3

2

1

5

5

6

7

8

9

10 11

5

5

6

7

8

9

10 11

SEE NOTE 3

SEE NOTE 3

SEE NOTE 3

Model AD-3I or AD-3ILP

Model AD-3XRI or AD-3XRILP

Model AD-3XRI or AD-3XRILP

NOT

USED

TERMINAL

BLOCK

RED

BLACK

WIRE NUT

REQUIRED

NOT USED

NOT USED

RELAY

BOARD

ALARM CONTACTS

125 VAC/24 VDC, 3A

SEE NOTES 1 AND 2

ALARM CONTACTS

125 VAC/24 VDC, 3A

SEE NOTES 1 AND 2

TO NEXT

ADDRESSABLE

DEVICE

OPTIONAL

REMOTE ALARM

INDICATOR

MODEL RLI-1

OR RLI-2

ZONE WIRES FROM SIEMENS BUILDING

TECHNOLOGIES, INC. LISTED MXL

CONTROL PANEL OR ICON-1 (IXL)

+

+

+

+ +

+

+

+ _

_

-

-

-

_

-

Figure 7

Typical Connections for Models AD-3XRI and AD-3XRILP

when used with MXL or ICON-1 (IXL)

address. Program each detector using the Model FPI-32 Programmer/

Tester. See the FPI-32 Manual, P/N 315-090077.

Installation

Align the detector alarm LED with the LED imprint located within the

detector compartment on the housing. Rotate the detector counterclock-

wise while pushing on the detector until it drops in place. Next, push and

rotate clockwise to engage the electrical connections. The detector auto-

matically stops and locks in place.

Removal

To remove the detector, push on the detector and rotate it counterclockwise

until the stop is reached. Then pull the detector out of the base to disengage.

Sensing Compartment Cover Installation

a. Install the cover gasket (Figure 3, 16) on the housing, if not already

installed. Be certain the alignment holes in the cover gasket are aligned

with the guides on the housing.

b. Install the sensing compartment ionization cover (17) when using DI-BX3,

DI-BX3H, ID-60IB, ID-60IBH, ILI-1B, or ILI-1BH detectors and the photo-

electric cover (18) when using an ILP-1 detector.

metal ground strap, using the proper conduit locking nuts. 

Failure to

provide proper grounding may result in fatal electrical shock and

caused non-conformance with national and local codes.

3. Use ID-60IB, ID-60IBH, ILI-1BH, and ILP-1 detectors only.

NOTES:

1. The relay contacts are shown just after a reset pulse, which

represents the non-alarm condition.

2. If the relay contacts are being used to control 120 VAC operated

equipment, ensure that the conduit is properly attached to the internal

Содержание CEREBRUS PYROTRONICS AD-3XRI

Страница 1: ...or infor mation on compatible detectors When smoke or combustion products are detected shutdown of the duct system and or operation of supplementary equipment is provided by the related system control panel TECHNICAL DATA Smoke Detector Compatibility TABLE 1 AD 3XRI COMPATIBILITY System Module Compatible Detectors System XL3 DI BX3 DI BX3H ID 60IB ID 60IBH ILI 1B ILI 1BH MXL Control Panel ID 60IB ...

Страница 2: ...e o g s e h s a l f m r o n n i f f o v p u s e e S L X I M E T S Y S N O I T A L L A T S N I E C I V R E S D N A L A U N A M 1 7 3 2 9 0 5 1 3 N P TABLE 4 AIR DUCT CONDITIONS Temperature Range 32O F 0O C 100O F 38O C per UL 268 268A Altitude Range Model Detectors Range AD 3XRI DI BX3 ID 60IB ILI 1B 0 4000 feet DI BX3H ID 60IBH ILI 1BH 3000 8000 feet AD 3XRILP No altitude limitations Relative Humi...

Страница 3: ...ers used After a fire is extinguished and all products of combustion are cleared from the duct system each system can be reset at its respective control panel and the XL3 also can be reset at its optional printer if available Trouble Condition A trouble condition from an AD 3XRI 3XRILP is indicated by visual and audible system devices connected to the control panel in an XL3 IXL or MXL Control Pan...

Страница 4: ...tector should when possible be located a minimum of six duct widths downstream from the source of the turbulence See Figure 1 A 12 inch by 12 inch access hole should be cut in the duct adjacent to the de tector to permit checking and cleaning of the sampling tubes if necessary Locate the air duct detector in the air handling system as shown in Figure 2 and in conformance with NFPA Pamphlet No 90A ...

Страница 5: ...ed on the template d Attach the appropriate model housing to the air duct using two No 10 11 2 inch screws 6 and also using two No 10 1 inch screws 7 with lockwashers 8 e Cut a 12 inch by 12 inch access hole in the duct adjacent to the housing to permit checking and cleaning of the sampling tubes The access hole must be covered and sealed when not in use Sampling Tube Selection To ensure accurate ...

Страница 6: ...r Stopper 10 Bracket 11 Screw 3 16 12 Screw 8 32 13 Plug 14 Detector DI BX3 DI BX3H ID 60IB ID 60IBH ILI 1B and ILI 1BH 15 Detector ILP 1 16 Cover Gasket 17 Ionization Detector Cover 18 Photoelectric Detector Cover P N 305 093076 19 Screw No 6 20 Sensitivity Test Jack Lid Figure 3 Exploded View CAUTION DISCONNECT POWER PRIOR TO SERVICING AIR DUCT DETECTOR DETECTOR ...

Страница 7: ...from the end with the four mount ing holes d Trim tube to the correct length remove all burrs and insert a rubber stopper Figure 3 Item 9 in the tube Installation of the Sampling Tubes a Before installing the tubes cut a 7 8 inch hole in the duct wall that is directly opposite the inlet sampling chamber hole in the detector hous ing This will allow the inlet tube to protrude through the duct b Att...

Страница 8: ...ermitted by the local building codes MXL Control Panel See Figure 7 Use two wire circuits of 18 AWG limited energy shielded cable without conduit if permitted by the local building codes IXL System ICON 1 See Figure 7 Use two wire circuits of 18 AWG limited energy shielded cable without conduit if it is permitted by the local building codes Control of Normally Energized and De Energized Devices Th...

Страница 9: ...ammed to respond at a specific and unique system 4 3 2 1 5 5 6 7 8 9 10 11 5 5 6 7 8 9 10 11 SEE NOTE 3 SEE NOTE 3 SEE NOTE 3 Model AD 3I or AD 3ILP Model AD 3XRI or AD 3XRILP Model AD 3XRI or AD 3XRILP NOT USED TERMINAL BLOCK RED BLACK WIRE NUT REQUIRED NOT USED NOT USED RELAY BOARD ALARM CONTACTS 125 VAC 24 VDC 3A SEE NOTES 1 AND 2 ALARM CONTACTS 125 VAC 24 VDC 3A SEE NOTES 1 AND 2 TO NEXT ADDRE...

Страница 10: ...tate clockwise to engage the electrical connections The detector auto matically stops and locks in place Removal To remove the detector push on the detector and rotate it counterclockwise until the stop is reached Then pull the detector out of the base to disengage Sensing Compartment Cover Installation a Install the cover gasket Figure 3 16 on the housing if not already installed Be certain the a...

Страница 11: ... the smoke detectors should be done by qualified service personnel only Maintenance The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector If the air holes in the inlet sampling tube become restricted the unit cannot receive a proper air sample and performance is impaired It is recommended that the sampling tubes be check...

Страница 12: ...g smoke directly into the inlet tube Check that the fire alarm system is activated CAUTION If the fire alarm system is connected to a central station or fire department or has external devices such as fans extinguishers etc connected notify appropriate personnel and disconnect the external devices until all tests are completed After testing reset the system reconnect the devices and notify the per...