3
OPERATION
When the AD-3XRI/3XRILP (AD-3XRI
or
AD-3XRILP) is operating, a
sample of air is drawn from the duct and passed through the sampling
chamber at low velocity by means of the inlet sampling tube. The air
sample passes through the smoke detector mounted in the duct housing
and is exhausted back into the duct through the outlet sampling tube.
Alarm Indication
The XL3, IXL, and MXL Control Panels have LEDs for alarm indication
that are used with the AD-3XRI/3XRILP. Refer to Table 3 above.
The LED on the detector in alarm can also be turned on or off by system
command.
Alarm Condition
When used with the XL3, IXL, or MXL Control Panel, the Model AD-3XRI/
3XRILP operates directly from the control panel. An alarm condition on
either of these systems is indicated by visual and audible system devices.
On XL3 Systems the alarm is also indicated on the DAX module and any
optional printers used. On MXL Control Panels the alarm is indicated on
the MKB-1/-2 and on any optional printers used.
After a fire is extinguished, and all products of combustion are cleared
from the duct system, each system can be reset at its respective control
panel, and the XL3 also can be reset at its optional printer, if available.
Trouble Condition
A trouble condition from an AD-3XRI/3XRILP is indicated by visual and
audible system devices connected to the control panel in an XL3, IXL, or
MXL Control Panel, depending on the type of system in which it occurs.
It can also be indicated by an optional printer. Call your Authorized
Siemens Building Technologies, Inc. Service Representative when a
trouble occurs.
For further information, refer to the appropriate Operation Instructions:
System XL3
OPERATION INSTRUCTIONS,
P/N 315-082989
MXL/MXLV Control Panel
OPERATION INSTRUCTIONS,
P/N
315-092117
System IXL
OPERATING INSTRUCTIONS,
P/N 315-079651
MOUNTING THE AIR DUCT HOUSING
Location on Duct System
Locate the air duct detector in the main supply duct, downstream from the
filters and positioned so as to operate reliably in case of smoke in any
part of the air stream. In instances where filters are capable of removing
smoke, install detectors both upstream and downstream from the filters.