![Siemens Cerberus PRO FS720 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/siemens/cerberus-pro-fs720/cerberus-pro-fs720_components-spare-parts-repair-parts_379139009.webp)
Stand-alone fire control panels
9
Building Technologies
A6V10227652_i_en_--
Fire Safety
2016-05-30
2.2.4 Housing Standard (empty)
FH7202-Z3
Housing (Standard)
Part no.
S54400-B70-A1
Application
–
Empty housing for open application, e.g. additional batteries, for operating add-on or for the event
printer.
–
Space for batteries
–
2 x FA2003-A1 (7 Ah) or
–
2 x FA2004-A1 (12 Ah) or
–
2 x FA2006-A1 (26 Ah)
Technical data
Dimensions (W x H x D)
430 x 398 x 160 mm
Color
–
Housing
grey, ~RAL 7035
–
Cover
grey, ~RAL-Design 050 00 00
Protection category
IP30
2.2.5 Auxiliary power supply
FP2003-A1
Power supply kit (70 W)
Part no.
A5Q00016005
Application
Auxiliary power supply to all stations (control panels and terminals).
Function
Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Technical data
Mains voltage
85…265 VAC
Current
0.5…1 A
Power consumption
Max. 90 VA
Dimensions (W x H x D)
95 x 170 x 54 mm
FP2004-A1
Power supply kit (150 W, A)
Part no.
A5Q00020825
Application
–
Power supply kit (150 W, A) as auxiliary power supply for installation into empty housing.
Function
Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Technical data
Mains voltage
230 VAC
Current
1.2 A
Power consumption
Max. 300 VA
Dimensions (W x H x D)
130 x 150 x 70 mm