![Siemens Cerberus PRO FS720 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/siemens/cerberus-pro-fs720/cerberus-pro-fs720_components-spare-parts-repair-parts_379139016.webp)
Networkable fire control panels
16
Building Technologies
A6V10227652_i_en_--
Fire Safety
2016-05-30
3.5
Expansion for fire control panels FC722, FC723, FC724 and
FC726
3.5.1 License
keys
FCA2033-A1
License key (S1)
Part no.
S54400-P154-A1
FCA2034-A1
License key (S2)
Part no.
S54400-P155-A1
FCA2035-A1
License key (S3)
Part no.
S54400-P156-A1
Application
S1
iButton
S2
iButton
S3
iButton
–
New series of license keys to support the growing number of applications
–
Replaces license keys L1 and L2.
–
Backward compatible
–
Type of installed license key is displayed in the Cerberus Engineering Tool
3.5.2 Event
printer
FTO2001-A1
Event printer
Part no.
A5Q00010126
Including cable for interface,
power supply and paper roll
Application
The event printer can be used in all control panels, terminals or in all empty housings if space is
available.
Function
The event printer is a thermal printer that logs alarms, faults and all messages.
–
The RS232 module FCA2001-A1 is required to operate the printer.
–
The RS232 module must be ordered separately.
Technical data
Operating voltage
DC 9…48 V
Operating current quiescent
at DC 9 V
at DC 48 V
50 mA
3 A
0.7 A
Interface
RS232 serial
Operating temperature
0…+50 °C
Storage temperature
-20… +70 °C
Humidity (no condensation permitted)
≤95 % rel.
Dimensions (W x H x D)
85 x 85 x 55 mm
3.5.3 Mounting
plate
FHA2007-A1
Mounting plate
Part no.
A5Q00010151
Features
The mounting plate can pivot allowing access to the underlying module. E.g. to mount the fire brigade
periphery module or the sounder modules.
–
Screwed on to the back wall of the housings.
Technical data
Dimensions (W x H x D)
221 x 241 x 46 mm