Networkable fire control panels
21
Building Technologies
A6V10227652_i_en_--
Fire Safety
2016-05-30
3.5.14 I/O card (RT)
FCI2007-A1
I/O card (RT)
Part no.
S54400-A20-A1
Application
For the transmission of alarms and faults. The card is mounted in the card cage (5 slots) of the fire
control panel FC726.
2x monitored outputs for RT alarm / Horns
1x relay output RT alarm
1x monitored output RT fault
1x relay output RT fault
2x I/O
–
I Exchange of defective cards possible during operation (Hot Plug)
Technical data
Input current
max. 4 A
Programmable inputs/outputs
8
3.5.15 I/O card (programmable)
FCI2008-A1
I/O card (programmable)
Part no.
S54400-A6-A1
Application
The I/O card is an additional card with programmable inputs and outputs for expansion of the integrated
inputs and outputs.
–
Is mounted in card cage (5 slots) of FC726 fire control panel.
Technical data
Input current
max. 2 A
Programmable inputs/outputs
12
3.5.16 I/O card (horn/monitored)
FCI2009-A1
I/O card (horn/monitored)
Part no.
S54400-C103-A1
Application
For 8 monitored horn lines or monitored outputs. The card is mounted in the card cage (5 slots) of the
fire control panel FC726.
Configurable as supervised horn outputs / flashing lights or fire controls,
Max. 2 A / output,
Max. 4 A / card
–
I Exchange of defective cards possible during operation (Hot Plug)
Technical data
Input current
max. 4 A
Programmable outputs
8