background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-033035-6

3

“IN” or “OUT” of the enclosure to perform this installation procedure. If the Mount-
ing Plate is located “IN” the enclosure you will have to gain access to it by opening
the enclosure Inner and Outer doors. If the Mounting Plate is located outside of the
enclosure, place it in front of you so that the word “TOP” is at the top and away from
you.

Each row of studs in the backbox or each Mounting Plate can hold a maximum of
two CC-5 cardcages. There are three possible locations for mounting the CC-5.

1.

Flush left in the backbox or on the Mounting Plate in positions 1-2.

2.

In the center of the row in the backbox or on Mounting Plate in positions 2-3.

3.

Flush right in the backbox or on the Mounting Plate in positions 3-4.

The CC-2 is most effectively used to add two more card slots in a row that already
has one CC-5 and another 1-position module (i.e., PSC-12). It is best installed in a
position adjacent to the CC-5.

When only one CC-5 cardcage is to be installed, it is normally installed on the left
side of a row in the backbox or on the Mounting Plate.

There is a top and bottom to the Mounting Plate. The top is where the word “TOP” is

stamped on the Mounting Plate. When the cardcage is mounted correctly on the

Mounting Plate it will be flush on the top, bottom, and left with the Mounting Plate

and the two screw holes in the center of the cardcage motherboard will be over

threaded posts.

1.

Install four 10-32 screws in the threaded posts at the top left of Position 1,
top right of Position 2, bottom left of Position 1, and the bottom right of
Position 2 on the Mounting Plate. Screw each of the 10-32 screws into the
threaded posts 5-6 turns. (Refer to Figure 3.)

2.

Place the cardcage over the four screws on the Mounting Plate and slide it
down or towards you to rest on the four screws. (Refer to Figure 4.) When
the cardcage is in the correct position it will be flush with the top, bottom,
and left side of the Mounting Plate.

3.

Install the two 10-32 screws in the center of the cardcage motherboard
near the left and right edge.

4.

Tighten the six screws.

Содержание CC-5

Страница 1: ...ctly to the top of the cardcage while internal power is connected to the bottom of the cardcage The two removable terminal block connectors at the top of each slot are arranged in two rows The lower row is labeled 1 through 8 and the upper row is labeled 9 through 16 These removable terminal block connectors are used for connecting power limited external equipment The removable terminal block conn...

Страница 2: ...e upper card guide has a label on each slot that can be used to identify the module installed in the slot If desired complete the label before inserting the upper card guide 2 Insert the upper card guide and secure with the captive screws 3 Insert the lower card guide and secure with the captive screws GUIDE PIN GUIDE PIN HOLE CAPTIVE SCREW RETAINERS CAPTIVE SCREWS LABELS LOWER CARD GUIDE UPPER CA...

Страница 3: ...on adjacent to the CC 5 When only one CC 5 cardcage is to be installed it is normally installed on the left side of a row in the backbox or on the Mounting Plate There is a top and bottom to the Mounting Plate The top is where the word TOP is stamped on the Mounting Plate When the cardcage is mounted correctly on the Mounting Plate it will be flush on the top bottom and left with the Mounting Plat...

Страница 4: ...POSTS POSITION 1 POSITION 3 POSITION 4 POSITION 2 POSITION 1 POSITION 3 POSITION 4 POSITION 2 CAB MP Figure 4 Location Of The CC 5 and CC 2 On The Optional CAB MP TOP SLIDE DOWN CARDCAGE UNTIL FLUSH ON TOP LEFT AND BOTTOM CAB MP CC 5 CARDCAGE CC 2 CARDCAGE INSTALL TWO 10 32 SCREWS WHEN ALIGNED WITH THREADED STUDS Figure 5 Mounting The CC 5 and CC 2 On The Optional CAB MP ...

Страница 5: ...ble Terminal Block On The CC 5 and CC 2 To Connect The Data Bus The Data bus connectors on the cardcage motherboard are P1 and P2 Refer to Figure 7 They are 60 pin keyed male connectors with connector extractors 1 Open the connector ejectors out of the vertical position and away from the connector body 2 Insert the female cable connector into the male connector P1 or P2 on the cardcage motherboard...

Страница 6: ...Control Modules SCM Control Modules FCM Master Voice Microphone LVM and Master Firefighters Telephone FMT The connector is keyed and requires no special instructions for cable connec tion Use cable CCL P N 500 634214 to connect from CAN bus P3 on CC 5 and CC 2 to the desired module CAN power must be supplied to E11 CC 5 or E5 CC 2 Refer to Figure 8 for wiring details CONNECTOR EJECTORS IN VERTICAL...

Страница 7: ...s The PSC 12 supplies the power to the two 60 pin Data bus connectors P1 and P2 in the CC 5 and CC 2 The total rating on P1 and P2 for all CC 5s in any given enclosure is as follows 24 VDC 2 Amps max 6 2 VDC 2 Amps max See PSC 12 Installation Instructions P N 315 033060 and the PSX 12 Installation Instructions P N 315 034050 for complete power supply loading calculations ...

Страница 8: ... concept It is however necessary to implement and maintain a comprehensive state of the art security concept that is customized to individual security needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may i...

Отзывы: