Chapter 3 – Point Database
19
Siemens Industry, Inc.
Owner's Manual
125-5093
Building Technologies
2015-10-14
Descriptor
Address
1
Application
Description
AO2 RANGE
90
6741, 6742
Scaling for the Analog Output (AO2) point. To get the correct
output, the slope and intercept of this point must match the
point database of the room controller.
AO2 DEADBAND
91
6740, 6741, 6742
When EXH FLOW and FLOW STPT are different by more
than the AO2 DEADBAND, the AO2 FLOW SIG changes
from setpoint to actual flow.
AO2 V MIN
92
6740, 6741, 6742
Minimum voltage value for fume hood output range (typically
0.0V or 1.0V).
CAL AIR
94
All
YES commands the controller to go through calibration
sequence for the air velocity transducers. YES is also
displayed when the calibration sequence is started
automatically. CAL AIR automatically returns to NO after the
calibration sequence is completed. Valid input: YES or NO.
CAL SETUP
95
All
The configuration setup code for the calibration sequence
options.
CAL TIMER
96
All
Time interval, in hours, between the calibration sequence
initiations if a timed calibration option is selected in CAL
SETUP.
AVS1 PRESS
97
All
The pressure that is applied to AVS1.
LOOP TIME
98
6741, 6742
The time, in tenths of a second, between control loop
calculations.
ERROR STATUS
99
All
The status code that indicates any errors detected during
controller power-up.
DISPLAY WT
106
6740, 6741, 6742
Factor used to filter out large changes in the value of FACE
VEL that is displayed at the ODP. This value is a percent that
is used to average a portion of the current average face
velocity with a portion of the previous average face velocity.
The value of this point is a percentage of the current average
face velocity. (Application 6740 uses EXH VOL.)
DISPLAY RES
107
6740, 6741, 6742
A change of value (COV) limit for the face velocity displayed
at the ODP. The display does not update unless the change
in face velocity exceeds this value.
BLANK DISPLY
108
6740, 6741, 6742
When set to YES, the face velocity does not display at the
ODP.
LAMP TEST
109
6740, 6741, 6742
Turns on all lights, prompts, and the audible alarm at the
ODP.
ENG UNITS
110
6740, 6741, 6742
Toggles the display of the ODP from feet per minute to
meters per second. Toggling this point does not change the
displayed value at the portable operator's terminal.
TABLE VOLTS
118
6740, 6741, 6742
The database point used to view and edit the internal Venturi
calibration data.
TABLE FLOW
119
6740, 6741, 6742
The database point used to view and edit the internal Venturi
calibration data.
V TABLE PT
120
6740, 6741, 6742
The database point used to view and edit the internal Venturi
calibration data.
HI LIMIT
121
6740, 6741, 6742
Determines when the flow PID will “coast” if near setpoint.
LO LIMIT
122
6740, 6741, 6742
Determines when the flow PID will “coast” if near setpoint.
EMER DI6
123
6740, 6741, 6742
Remote initiation of the Emergency Purge functionality.
OPEN LOOP
124
6742
The controller does not use feedback to reposition the air