Chapter 3 – Point Database
17
Siemens Industry, Inc.
Owner's Manual
125-5093
Building Technologies
2015-10-14
Descriptor
Address
1
Application
Description
DO 7
47
6700
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
AUTOZERO DO8
48
6740, 6741, 6742
Drives the Offboard Air Module(s) in order to calibrate the
flow sensor(s). Do not use or manually set this point.
DO 8
48
6700
Spare digital output controls a 24 Vdc load with an ON or
OFF status.
AI 3
49
6741, 6742
Optional input for External Face Area or Airflow sensor.
AI 3
49
6700, 6740
Optional input for Airflow sensor or spare analog input (0 –
10V or 4-20 mA).
AI 4
50
6741, 6742
Sash sensor 2 input or spare analog input (0 - 10V or 4-20
mA).
AI 4
50
6700,, 6740
Startup DI 4 (Point 56) or spare analog input (0 – 10V or 4-20
mA).
AI 5
51
6741, 6742
Sash sensor 1 input.
AI 5
51
6700, 6740
Spare analog input, 10K
Ω.
VERT SASH1
52
6741, 6742
Current position, in inches (cm), of the vertical sash wired as
sash 1 at the controller board. If not physically wired to the
controller, this point may display as 'failed'.
VERT SASH2
53
6741, 6742
Current position, in inches (cm), of the vertical sash wired as
sash 2 at the controller board. If not physically wired to the
controller, this point may appear as 'failed'.
FACE AREA
54
6741, 6742
The open area, in square feet (SQM), of the fume hood face,
which includes the fixed area and accounts for the bypass
area.
CAL SASH POS
55
6741, 6742
User defined value used during calibration of the sash sensor
to describe the current position of the sash, in inches (cm).
CAL SASH LOC
56
6741, 6742
User defined value (MIN or MAX) used during the calibration
sequence to indicate if the minimum or maximum sash
position is being calibrated.
DI 4
56
6740
DI determines if DI 4 is used to change the STARTUP
MODE.
CAL SASH NUM
57
6741, 6742
The number of the sash being calibrated. Valid values: 1 to
5.
DMPR COMD
58
6740, 6741, 6742
The commanded position of the damper.
INVERT DO2
59
6740, 6741
Setting to NCLOSE allows the controller to operate industry
standard floating control actuators. Setting this point may
stop the failsafe operation from functioning.
AVS FAILMODE
60
6740, 6741, 6742
Indicates the desired position of the damper if the airflow
sensor(s) fail.
Valid values: CLOSED or OPEN.
EXH P GAIN
61
6740, 6741, 6742
The proportional gain value for the fume hood flow control
loop.
EXH I GAIN
62
6740, 6741, 6742
The integral gain value for the fume hood flow control loop.
EXH D GAIN
63
6740, 6741, 6742
The derivative gain value for the fume hood flow control loop.
FIXED AREA
64
6741, 6742
Open area of the fume hood, in square feet (SQM), that
remains the same regardless of sash position.
VERT WIDTH1
65
6741, 6742
Defines the overall width of the vertical sash wired to sash 1