Data Library
2.8 Event Log Pointers
ATC5300
26
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02
2.8
Event Log Pointers
(To be used with function 04)
2.9
Event Log
(To be used with function 04)
¿
The meaning of the event code can be found in the following table. In case there is no
recorded event code 0 will be returned.
2.9.1
Event Log - Numeric Code / Event Type Correspondence
ADDRESS WORDS
PARAMETER
RANGE
FORMAT
2510h
1
Pointer to the most recent event
position
0 ..99
Unsigned integer
2511h
1
Counter of the stored events
number
0 ..99
Unsigned integer
ADDRESS WORDS
PARAMETER
RANGE
FORMAT
2100h
1
Event pos. 1 - Hours / Minutes
0
…
23 / 0
…
59 Unsigned integer
2101h
1
Event pos. 1 - Seconds / Day
0
…
59 / 0
…
31 Unsigned integer
2102h
1
Event pos. 1 - Month / Year
0
…
12 / 0
…
99 Unsigned integer
2103h
1
Event pos. 1 - Event code
¿
1
…
225
Unsigned integer
2104h
1
Event pos. 2 - Hours / Minutes
0
…
23 / 0
…
59 Unsigned integer
2105h
1
Event pos. 2 - Seconds / Day
0
…
59 / 0
…
31 Unsigned integer
2106h
1
Event pos. 2 - Month / Year
0
…
12 / 0
…
99 Unsigned integer
2107h
1
Event pos. 2 - Event code
¿
1
…
225
Unsigned integer
—
—
—
—
—
228Ch
1
Event pos. 100 - Hours / Minutes
0
…
23 / 0
…
59 Unsigned integer
228Dh
1
Event pos. 100 - Seconds / Day
0
…
59 / 0
…
31 Unsigned integer
228Eh
1
Event pos. 100 - Month / Year
0
…
12 / 0
…
99 Unsigned integer
228Fh
1
Event pos. 100 - Event code
¿
1
…
225
Unsigned integer
Code
Event
1
ATC Power on
2
ATC Power off
3
ATC Reboot
5
Mode changed to RESET-OFF
6
Mode changed to MAN
7
Mode changed to AUT
8
Mode changed to TEST
10
External generator start (begin)
11
External generator start (end)
12
External transfer signal (begin)
13
External transfer signal (end)
20
Automatic test enabled
21
Automatic test disabled