ATC5300
Modbus Communication Protocol, Edition 03/2011, A5E02469001-02
17
Data Library
2
Data Library
2.1
Data Provided
Data provided by Serial Communication Protocol (to be used with functions 03 and 04)
ADDRESS WORDS
MEASURE
UNIT
FORMAT
02h
2
Voltage of line 1 L1-N
V
Unsigned long
04h
2
Voltage of line 1 L2-N
V
Unsigned long
06h
2
Voltage of line 1 L3-N
V
Unsigned long
08h
2
Voltage of line 1 L1-L2
V
Unsigned long
0Ah
2
Voltage of line 1 L2-L3
V
Unsigned long
0Ch
2
Voltage of line 1 L3-L1
V
Unsigned long
0Eh
2
Voltage of line 2 L1-N
V
Unsigned long
10h
2
Voltage of line 2 L2-N
V
Unsigned long
12h
2
Voltage of line 2 L3-N
V
Unsigned long
14h
2
Voltage of line 2 L1-L2
V
Unsigned long
16h
2
Voltage of line 2 L2-L3
V
Unsigned long
18h
2
Voltage of line 2 L3-L1
V
Unsigned long
1Ah
2
Frequency of line 1
Hz / 10
Unsigned long
1Ch
2
Frequency of line 2
Hz / 10
Unsigned long
1Eh
2
Battery voltage (DC power supply)
VDC / 10
Unsigned long
20h
2
Total operation time
s
Unsigned long
22h
2
Line 1 ok total time
s
Unsigned long
24h
2
Line 2 ok total time
s
Unsigned long
26h
2
Line 1 not ok total time
s
Unsigned long
28h
2
Line 2 not ok total time
s
Unsigned long
2Ah
2
Line 1 breaker closed total time
s
Unsigned long
2Ch
2
Line 2 breaker closed total time
s
Unsigned long
2Eh
2
Breaker opened total time
s
Unsigned long
30h
2
(not used)
—
Unsigned long
32h
2
Number of operations of line 1 breaker
in AUT
nr
Unsigned long
34h
2
Number of operations of line 2 breaker
in AUT
nr
Unsigned long
36h
2
Number of operations of line 1 breaker
in MAN
nr
Unsigned long