2.5
Equipment combinations
2.5.1
2-port / 3-port threaded valves with stroke actuator SAS..
Typical applications:
·
Heating plants
·
District heating plants
·
Ventilation and air conditioning plants
Actuators
Stroke
Positioning force
Data sheet
SAS..
5.5 mm
400 N
N4581
PN 16
VVG44..
PN 16
VXG44..
SAS..
Medium
1…120 °C
Medium
1…120 °C
DN
G
k
vs
∆
p
max
∆
p
s
Data sheet
N4364
Data sheet
N4464
[Inch]
[m
3
/h]
[kPa]
[kPa]
VVG44.15-..
1)
VXG44.15-..
1)
15
G 1 B
0.25 / 0.4 / 0.63
400
1600
VVG44.15-..
1)
VXG44.15-..
1)
15
G 1 B
1 / 1.6
400
725
VVG44.15-..
1)
VXG44.15-..
1)
15
G 1 B
2.5 / 4
400
400
VVG44.20-6.3
VXG44.20-6.3
20
G 1 1/4 B
6.3
400
750
VVG44.25-10
VXG44.25-10
25
G 1 1/2 B
10
400
400
VVG44.32-16
VXG44.32-16
32
G 2 B
16
250
250
VVG44.40-25
VXG44.40-25
40
G 2 1/4 B
25
125
125
PN 25
VVG55..
2)
SAS..
Medium
1…130 °C
DN
G
k
vs
∆
p
max
∆
p
s
Data sheet
N4379
[Inch]
[m
3
/h]
[kPa]
[kPa]
VVG55.15-..
1)
15
G 3/4 B
0.25 / 0.4 / 0.63
1200
2500
VVG55.15-..
1)
15
G 3/4 B
1 / 1.6 / 2.5
1200
2000
VVG55.20-4
20
G 1 B
4
1000
1000
VVG55.25-6.3
25
G 1 1/4 B
6.3
800
800
1)
.. = insert k
vs
value
2)
.. = VVG55 to be replaced by VVG549 as of January 1, 2017
2.5.2
2-port / 3-port threaded valves with stroke actuator SAS..
and SAT..
Typical applications:
·
District heating plants
Actuators
Stroke
Positioning force
Data sheet
SAS..
5.5 mm
400 N
N4581
SAT..
5.5 mm
300 N
N4584
PN 25
VVG549..
SAS..
1), 2)
SAT..
1)
Medium
2...130 °C
DN
G
k
vs
∆
p
max
∆
p
s
∆
p
max
∆
p
s
Data sheet
Q4380
[Zoll]
[m
3
/h]
[kPa]
[kPa]
[kPa]
[kPa]
VVG549.15-0.25
15
G 3/4 B
0,25
1200
2500
1200
2500
VVG549.15-0.4
0,4
VVG549.15-0.63
0,63
VVG549.15-1
1
1500
1500
VVG549.15-1.6
1,6
VVG549.15-2.5
2,5
VVG549.20-4K
3)
20
G 1 B
4
1600
1600
VVG549.25-6.3K
3)
25
G 1 1/4 B
6,3
1)
Briefly 150 °C (up to 150 °C max. 6 of 24 hours), with ALG..B fittings up to 100 °C
2)
SAS.. combined with VVG549: Change setting on the DIL switch to linear (factory setting = log).
SAS../MO: Change Modbus register 263 to 0 = linear
®
only possible with Firmware release 2.0, not
with 0.27 and 1.0!
3)
Pressure compensated