Specifications 

 

Power Requirements 

Commissioning Tool 

24 Vac nominal (20 to 30 Vac) at 50/60 Hz, 3 VA, Class 2 

 

Plug-in Transformer (provided) 

120 Vac at 60 Hz 

Input DC Feedback 

0 to 30 Vdc 

Electrical Connection 

Screw Terminals 

24 to 12 AWG 

 

Transformer Jack 

0.08 in. (2.11 mm) diameter pin, 0.25 in. (6.35 mm) diameter plug 

Input Impedance 

Voltmeter 

1 Megohm (nominal) 

Output Signal 

AC Power 

24 Vac nominal (20 to 30 Vac), 25 VA maximum (Terminals 1 and 2). 
Output AC voltage is equivalent to the input AC voltage and 
frequency.  

 

Resistive 

0 to 135 ohms ±7%, 2W or 0 to 1k ohms ±5%, 2W (Terminals 3, 4, 
and 5).  

 

Proportional 

Voltage 

 0 to 10 Vdc (500 ohms minimum); 0 to 20 Vdc 

(6.8k ohms minimum) (Terminals 2 and 3);  

Current 

 0 to 20 mA (680 ohms maximum) (Terminals 2 and 3).  

 

Floating Control 

24 Vac nominal (20 to 30 Vac), 25 VA maximum (Terminals 2, 3, 
and 4). Output AC voltage is equivalent to the input AC voltage and 
frequency.  

 

Bias 

5 Vdc with 330 ohm series resistor (Terminal 6).  

Accuracy 

 2% of full scale at 77°F (25°C) 

Resolution 

0.1 Vdc, 0.1 mA 

Auxiliary Switch 
Testing 

Provides 24 Vac at 4 mA to auxiliary switch contacts (dry contacts only). 

Response Time 

Proportional, Voltage 

0 to 20 Vdc in 20 seconds 

 

Proportional, Current 

0 to 20 mA in 20 seconds 

Ambient Conditions 

Operating 

4 to 122°F (

20 to 50°C); 10 to 90% RH, non-condensing 

 

Storage 

40 to 158°F (

40 to 70°C); 5 to 95% RH, non-condensing 

Dimensions 
(H x W x D) 

Commissioning Tool (overall) 

7.7 in. x 4.5 in. x 2.2 in. (196 mm x 113 mm x 55 mm) 

 

Transformer 

4.2 in. x 3.0 in. x 2.4 in. (107 mm x 76 mm x 61 mm) 

 

Carrying Case 

10.4 in. x 12.7 in. x 4.2 in. (263 mm x 322 mm x 107 mm) 

Weight 

Commissioning Tool  

0.9 lb (0.4 kg) 

 

Transformer 

1.7 lb (0.8 kg) 

 

Carrying Case 

2.0 lb (0.9 kg) 

Total Shipping Weight  5.4 lb (2.5 kg) 

The performance specifications are nominal and conform to acceptable industry standards. Siemens Building Technologies, Inc. 
shall not be liable for damages resulting from misapplication or misuse of its products.  

Содержание 985-047

Страница 1: ... DC voltage and current for controlling an actuator It requires no controller hook up which makes equipment calibration setup and adjustment a quick and easy process Figure 1 Actuator Commissioning Tool Features and Benefits Universal Compatibility Works with all Siemens actuators most competitors actuators and other voltage current or resistance controlled equipment Compact Portable Unit Allows e...

Страница 2: ...l 24 Vac nominal for use with floating control and on off actuators The resistive mode is the default operating mode when the commissioning tool is not powered To select other operating modes the ON OFF switch must be turned ON LEDs indicate which mode is active The Commissioning Tool also provides additional testing features as follows Table 2 Additional Testing Features Feature Function Power fo...

Страница 3: ...igher voltages could damage the device Powering a Non externally Powered Actuator or Control Device CAUTION Equipment Damage Hazard Controlled equipment loading from Terminals 1 and 2 must be limited to 25 VA maximum NOTE For 115 230 Vac actuators the Commissioning Tool can be used to provide signal but must be externally powered 1 To provide a 24 Vac nominal power signal connect Terminals 1 24 Va...

Страница 4: ...or a procedure to apply power to the Commissioning Tool 5 If the resistive mode green LED Figure 7 does not light depress the SELECT MODE pushbutton to activate the resistive mode The green LED should then light and indicate that the resistive mode is active 6 Turn the dial Figure 7 to adjust the level of resistance Figure 7 Resistive Mode Proportional Voltage Mode Vdc 1 To supply a 0 to 20 Vdc si...

Страница 5: ...ing Tool section for a procedure to apply power to the Commissioning Tool 5 Depress the SELECT MODE pushbutton to activate the current mode A green LED should light and indicate that the current mode is active Figure 11 6 Use the rocker switch located on the upper left side of the Commissioning Tool Figure 11 to adjust the current level from 0 to 20 mA The digital display shows the level of the ou...

Страница 6: ...tput from the Commissioning Tool during the proportional voltage and current modes NOTE During the floating control or resistive modes the digital display is not used and reads zero DC Feedback Display Mode CAUTION Equipment Damage Hazard Do not apply signals greater than 30 Vdc or any AC signals to Terminal 7 DC FEEDBACK or damage to the Commissioning Tool can result When the OUTPUT DC FEEDBACK t...

Страница 7: ...C voltage applied between Terminal 7 DC FEEDBACK and Terminal 8 COM Auxiliary Switch Testing CAUTION Equipment Damage Hazard Do not apply power to the switch being tested or to the Commissioning Tool auxiliary switch inputs The Commissioning Tool provides a signal to the switch contacts being tested Auxiliary switch testing can be used independently or while supplying a control signal to the field...

Страница 8: ... ohms 7 2W or 0 to 1k ohms 5 2W Terminals 3 4 and 5 Proportional Voltage 0 to 10 Vdc 500 ohms minimum 0 to 20 Vdc 6 8k ohms minimum Terminals 2 and 3 Current 0 to 20 mA 680 ohms maximum Terminals 2 and 3 Floating Control 24 Vac nominal 20 to 30 Vac 25 VA maximum Terminals 2 3 and 4 Output AC voltage is equivalent to the input AC voltage and frequency Bias 5 Vdc with 330 ohm series resistor Termina...

Отзывы: