Siemens 985-047 Скачать руководство пользователя страница 2

129-287 
Operating Instructions  
Rev. 1, October, 1999 
 

Page 2 of 8

 

Siemens Industry, Inc.

 

Installation Conventions 

WARNING 

 

Personal injury/loss of life may 
occur if a procedure is not 
performed as specified. 

CAUTION 

 

Equipment damage, or loss of 
data may occur if the user 
does not follow procedure as 
specified. 

 

 

Figure 2.  Actuator Commissioning Tool, Carrying 

Case, Plug-in Transformer, and Three Extra Terminal 

Blocks.  

 

Application Overview 

The Actuator Commissioning Tool has 
four pushbutton selectable modes of operation as 
follows: 

Table 1.  Output Control Signal Features.  

Mode of 

Operation 

Description 

Resistive * 

0 to 135 ohms or 0 to 1k ohms for 
use with resistive input actuators. 

Voltage 

0 to 20 Vdc for use with 
proportional actuators 

Current 

0 to 20 mA for use with 
proportional actuators 

Floating Control 

24 Vac (nominal) for use with 

floating control and on/off 
actuators 

*  The resistive mode is the default operating 

mode when the commissioning tool is not 
powered. To select other operating modes, the 
ON/OFF switch must be turned ON. LEDs 
indicate which mode is active. 

 

The Commissioning Tool also provides additional 
testing features as follows: 
 

Table 2.  Additional Testing Features.  

Feature 

Function 

Power for Actuators 

A 24 Vac (nominal) signal is 
provided to power actuators that 
are not externally powered. 

Bias (for feedback 
potentiometers) 

A 5 Vdc bias signal is provided 
through a 330 ohm resistor for 
resistive feedback testing (for 
feedback potentiometers).  

Voltmeter 

Measures 0 to 30 Vdc signal.  

Switch Testing 

LEDs display auxiliary contact 
closure.  
Use with dry contacts only! 

 
The Commissioning Tool receives power by either: 

 

Applying 24 Vac (nominal) to the INPUTS 
terminal block, or 

 

Connecting the 120V plug-in transformer 
(provided) to its power jack.  

 

Dimensions 

 

Figure 3.  Commissioning Tool Dimensions (in./mm).  

 

Содержание 985-047

Страница 1: ... DC voltage and current for controlling an actuator It requires no controller hook up which makes equipment calibration setup and adjustment a quick and easy process Figure 1 Actuator Commissioning Tool Features and Benefits Universal Compatibility Works with all Siemens actuators most competitors actuators and other voltage current or resistance controlled equipment Compact Portable Unit Allows e...

Страница 2: ...l 24 Vac nominal for use with floating control and on off actuators The resistive mode is the default operating mode when the commissioning tool is not powered To select other operating modes the ON OFF switch must be turned ON LEDs indicate which mode is active The Commissioning Tool also provides additional testing features as follows Table 2 Additional Testing Features Feature Function Power fo...

Страница 3: ...igher voltages could damage the device Powering a Non externally Powered Actuator or Control Device CAUTION Equipment Damage Hazard Controlled equipment loading from Terminals 1 and 2 must be limited to 25 VA maximum NOTE For 115 230 Vac actuators the Commissioning Tool can be used to provide signal but must be externally powered 1 To provide a 24 Vac nominal power signal connect Terminals 1 24 Va...

Страница 4: ...or a procedure to apply power to the Commissioning Tool 5 If the resistive mode green LED Figure 7 does not light depress the SELECT MODE pushbutton to activate the resistive mode The green LED should then light and indicate that the resistive mode is active 6 Turn the dial Figure 7 to adjust the level of resistance Figure 7 Resistive Mode Proportional Voltage Mode Vdc 1 To supply a 0 to 20 Vdc si...

Страница 5: ...ing Tool section for a procedure to apply power to the Commissioning Tool 5 Depress the SELECT MODE pushbutton to activate the current mode A green LED should light and indicate that the current mode is active Figure 11 6 Use the rocker switch located on the upper left side of the Commissioning Tool Figure 11 to adjust the current level from 0 to 20 mA The digital display shows the level of the ou...

Страница 6: ...tput from the Commissioning Tool during the proportional voltage and current modes NOTE During the floating control or resistive modes the digital display is not used and reads zero DC Feedback Display Mode CAUTION Equipment Damage Hazard Do not apply signals greater than 30 Vdc or any AC signals to Terminal 7 DC FEEDBACK or damage to the Commissioning Tool can result When the OUTPUT DC FEEDBACK t...

Страница 7: ...C voltage applied between Terminal 7 DC FEEDBACK and Terminal 8 COM Auxiliary Switch Testing CAUTION Equipment Damage Hazard Do not apply power to the switch being tested or to the Commissioning Tool auxiliary switch inputs The Commissioning Tool provides a signal to the switch contacts being tested Auxiliary switch testing can be used independently or while supplying a control signal to the field...

Страница 8: ... ohms 7 2W or 0 to 1k ohms 5 2W Terminals 3 4 and 5 Proportional Voltage 0 to 10 Vdc 500 ohms minimum 0 to 20 Vdc 6 8k ohms minimum Terminals 2 and 3 Current 0 to 20 mA 680 ohms maximum Terminals 2 and 3 Floating Control 24 Vac nominal 20 to 30 Vac 25 VA maximum Terminals 2 3 and 4 Output AC voltage is equivalent to the input AC voltage and frequency Bias 5 Vdc with 330 ohm series resistor Termina...

Отзывы: