Siemens 985-047 Скачать руководство пользователя страница 5

129-287 

Operating Instructions 

Rev. 1, October, 1999 

 

Siemens Industry, Inc.

 

Page 5 of 8 

6.

 

Use the rocker switch located on the upper left 
side of the Commissioning Tool (

Figure 9

) to 

adjust the voltage level from 0 to 20 Vdc. The 
digital display shows the level of the output 
voltage. (Adjustment increments increase 0.1V 
during the first five seconds and then increase 
rapidly after that, allowing for quick adjustment 
of the output control signal.) 

 

Figure 9.  Voltage Mode.  

 

Proportional Current Mode (mA) 

1.

 

To supply a 0 to 20 mA signal, connect 
Terminals 2 (COM) and 3 (mA) of the OUTPUTS 
terminal block to the actuator or device being 
controlled (

Figure 10

). Also see the appropriate 

actuator documentation for wiring application 
information. 

 

Figure 10.  Current Signal Connections.  

2.

 

If the actuator is externally powered, skip to 
Step 3.  
See the 

Powering a Non-externally Powered 

Actuator or Control Device

 section for a 

procedure to apply power to the device from the 
Commissioning Tool.  

3.

 

Use the toggle switch (

Figure 11

) to select the 

OUTPUT display mode. 

4.

 

See the 

Powering Commissioning Tool 

section 

for a procedure to apply power to the 
Commissioning Tool. 

5.

 

Depress the SELECT MODE pushbutton to 
activate the current mode. A green LED should 
light and indicate that the current mode is active 
(

Figure 11

).  

 

6.

 

Use the rocker switch located on the upper left 
side of the Commissioning Tool (

Figure 11

) to 

adjust the current level from 0 to 20 mA. The 
digital display shows the level of the output 
current. (Adjustment increments increase 
0.1 mA during the first five seconds and then 
increase rapidly after that, allowing for quick 
adjustment of the output control signal.) 

 

Figure 11.  Current Mode.  

 

Floating Control Mode (Vac) 

NOTE:

 

The digital display is not used and reads 
zero in this mode. 

1.

 

Connect Terminals 2 (COM), 3 (CCW), and 4 
(CW) of the OUTPUTS terminal block to the 
actuator or device being controlled (

Figure 12

). 

Connect Terminal 1 (24 Vac) for spring return 
actuators (

Figure 5

).  

NOTE:

 

On removal of the Terminal 1 connection, 
the actuator spring return activates. Also 
see the appropriate actuator 
documentation for wiring application 
information. 

 

Figure 12.  Floating Control Signal Connections.  

 

NOTE:

 

Verify that the toggle switch is in the 
STOP position (

Figure 13

.).  

2.

 

See the 

Powering Commissioning Tool 

section 

for a procedure to apply power to the 
Commissioning Tool. 

 

Содержание 985-047

Страница 1: ... DC voltage and current for controlling an actuator It requires no controller hook up which makes equipment calibration setup and adjustment a quick and easy process Figure 1 Actuator Commissioning Tool Features and Benefits Universal Compatibility Works with all Siemens actuators most competitors actuators and other voltage current or resistance controlled equipment Compact Portable Unit Allows e...

Страница 2: ...l 24 Vac nominal for use with floating control and on off actuators The resistive mode is the default operating mode when the commissioning tool is not powered To select other operating modes the ON OFF switch must be turned ON LEDs indicate which mode is active The Commissioning Tool also provides additional testing features as follows Table 2 Additional Testing Features Feature Function Power fo...

Страница 3: ...igher voltages could damage the device Powering a Non externally Powered Actuator or Control Device CAUTION Equipment Damage Hazard Controlled equipment loading from Terminals 1 and 2 must be limited to 25 VA maximum NOTE For 115 230 Vac actuators the Commissioning Tool can be used to provide signal but must be externally powered 1 To provide a 24 Vac nominal power signal connect Terminals 1 24 Va...

Страница 4: ...or a procedure to apply power to the Commissioning Tool 5 If the resistive mode green LED Figure 7 does not light depress the SELECT MODE pushbutton to activate the resistive mode The green LED should then light and indicate that the resistive mode is active 6 Turn the dial Figure 7 to adjust the level of resistance Figure 7 Resistive Mode Proportional Voltage Mode Vdc 1 To supply a 0 to 20 Vdc si...

Страница 5: ...ing Tool section for a procedure to apply power to the Commissioning Tool 5 Depress the SELECT MODE pushbutton to activate the current mode A green LED should light and indicate that the current mode is active Figure 11 6 Use the rocker switch located on the upper left side of the Commissioning Tool Figure 11 to adjust the current level from 0 to 20 mA The digital display shows the level of the ou...

Страница 6: ...tput from the Commissioning Tool during the proportional voltage and current modes NOTE During the floating control or resistive modes the digital display is not used and reads zero DC Feedback Display Mode CAUTION Equipment Damage Hazard Do not apply signals greater than 30 Vdc or any AC signals to Terminal 7 DC FEEDBACK or damage to the Commissioning Tool can result When the OUTPUT DC FEEDBACK t...

Страница 7: ...C voltage applied between Terminal 7 DC FEEDBACK and Terminal 8 COM Auxiliary Switch Testing CAUTION Equipment Damage Hazard Do not apply power to the switch being tested or to the Commissioning Tool auxiliary switch inputs The Commissioning Tool provides a signal to the switch contacts being tested Auxiliary switch testing can be used independently or while supplying a control signal to the field...

Страница 8: ... ohms 7 2W or 0 to 1k ohms 5 2W Terminals 3 4 and 5 Proportional Voltage 0 to 10 Vdc 500 ohms minimum 0 to 20 Vdc 6 8k ohms minimum Terminals 2 and 3 Current 0 to 20 mA 680 ohms maximum Terminals 2 and 3 Floating Control 24 Vac nominal 20 to 30 Vac 25 VA maximum Terminals 2 3 and 4 Output AC voltage is equivalent to the input AC voltage and frequency Bias 5 Vdc with 330 ohm series resistor Termina...

Отзывы: