Operation
162/214
Revision 11 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DA10 • 861-9601.9
1
Initial situation
2
➭ Push the interrogation lever downwards.
3
➭ Push the control gate to the right.
4
➭ Switch the three-position disconnector to READY-
TO-EARTH position (insert the operating lever for
the READY-TO-EARTH function and turn 180°
clockwise).
5
➭ Remove the operating lever for the READY-TO-
EARTH function.
The interrogation lever and the control gate return to
their initial position.
6
➭ Close the circuit-breaker to earth the feeder.