Final installation work
12.1
Mounting cables with plugs
!
Proceed according to the installation instructions of the corresponding plug
manufacturer.
!
Fit cable strain relieves. Distance between the lower edge of the flange dome and
the cable strain relief: 450 mm as a minimum.
!
Connect the cable shield at the cable strain relief.
12.2
Connecting low-voltage cables
!
Remove the metal covers from the frames.
!
Open the doors of the low-voltage compartments.
!
Fix the low-voltage cables at the holders provided for this purpose.
!
Connect the ends of the cables to the terminals in the low-voltage compartments
according to the circuit diagram.
!
Close the doors of the low-voltage compartments.
12.3
Mounting the metal covers
!
Screw all metal covers to the supporting frames again.
13
Tests
13.1
Checking the SF
6
-gas filling
Checking the gas pressure
Before commissioning or a rated short-duration power-frequency withstand voltage test
the gas pressures of
all
gas compartments must be checked.
!
On all gas compartments filled at site: After having filled the gas compartments,
observe a temperature compensation time of
24 hours
. Do not check the gas
pressure before that time.
!
Check the gas pressure in all gas compartments filled at site. If the limit values
adjusted on the indicators are underflown or exceeded, correct the gas pressure.
ATTENTION!
The dust-proof caps supplied on the sockets of the multiple panel connections do not
provide sufficient shock protection.
!
Close unused sockets of multiple panel connections with dummy plugs.
DANGER!
Operation with an incorrect SF
6
-gas pressure can destroy parts of the switchgear.
!
Do not put the switchgear into operation with too high or too low SF
6
-gas
pressures.