8. TROUBLE SHOOTING
Truck interlocking
Fault
Cause
Remedy
1) Truck can not be moved out of
panel.
Truck interlock closed
Open truck interlock
2) Door to switching device
compartment.
Interlocking lever of LV connector not
folded inwards
Fold interlocking lever inwards
Locking gates of guide rails not closed
Close locking gates of guide rails
Truck
Fault
Cause
Remedy
Double bit key can not be turned
with open door locking handle.
Circuit breaker in CLOSED position
Switch circuit breaker to OPEN position
Truck ca not be racked to
SERVICE position (mechanically).
Operating lever inserted in manual
CLOSE/OPEN operating mechanism of
feeder earthing switch
Remove operating lever
Feeder earthing switch not in OPEN
position
Switch feeder earthing switch to OPEN
position
General switchgear interlock active
Observe general switchgear interlock
Truck can not be racked to TEST
position.
Circuit breaker in CLOSED position
Switch circuit breaker to OPEN position
Double bit key can not be turned.
Feeder earthing switch
Fault
Cause
Remedy
Operating lever for earthing switch
can not be pushed in.
Switching device truck in SERVICE
position
Rack switching device truck to TEST
position
Hand crank for switching device truck
inserted
Remove hand crank for switching device
truck
Electromagnetic interlocking is active
Observe the electromagnetic interlocking
Circuit breaker
Fault
Cause
Remedy
Circuit breaker can not be closed
Hand crank for truck inserted
Remove hand crank for truck
Switching device truck is intermediate
position
Rack switching device truck to SERVICE
or TEST position
Spring not charged
Wait for 15 s (motor) or charge manually
Under voltage release not activated
Energize the under voltage release
Low voltage connector not plugged in
Plug low voltage connector in
Spring energy store is not
charged automatically
No control voltage
Apply control voltage or charge spring
energy store manually