Setting the Transmission Rate
You can set the transmission rate using the jumpers BR1 and BR2.
i
i
NOTE
If you are using the communication converter for a differential protection or distance protection application
in a SIPROTEC protection device with a protection interface, the jumpers BR1 and BR2 must be plugged into
position 2-3 for 128 kBit/s (factory setting).
Table 3-1
Plug-In Positions
Transmission Rate
BR1
BR2
128 kBit/s
5
2-3
2-3
256 kBit/s
1-2
2-3
512 kBit/s
2-3
1-2
2048 kBit/s
1-2
1-2
[dw_jumper_BR1_BR2, 1, --_--]
Figure 3-3
Setting the Transmission Rate
3.3
5
For SIPROTEC devices
Application Examples and Configuration
3.3 Setting the Transmission Rate
22
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
C53000-B1174-C190-1, Edition 01.2022