English
7XV5662-0AA00/GG
52
C53000-B1174-C134-8
Isolation coordination according to IEC / EN / UL 61010-1 overvoltage category III, pollution
degree 2.
EMC Tests for Noise Emission
Standard
IEC/EN 61000-6-2 , IEC 60255 -22,
(product standards)
VDE 0435
For more standards see also individual
functions
1 MHz test, Class III IEC 60255-22-1, IEC
61000-4-18,
IEEE C37.90.1
2,5 kV (Peak); 1 MHz;
τ
= 15
μ
s; 400 Surges
per s; Test duration 2 s; Ri = 200
Ω
Electrostatic discharge, Class IV
IEC 60255-22-2, IEC 61000-4-2
8 kV contact discharge; 15 kV air discharge;
both polarities; 150 pF; Ri = 330
Ω
Radio frequency electromagnetic field, am-
plitude-modulated, Class III
IEC 60255-22-3, IEC 61000-4-3
10 V/m; 80 MHz to 2,7 GHz 80 % AM;
1 kHz
Fast transient bursts, Class IV
IEC 60255-22-4, IEC 61000-4-4,
IEEE C37.90.1
4 kV; 5 ns/50 ns; 5 kHz;
burst length = 15 ms; repetition rate 300 ms;
both polarities; Ri = 50
Ω
; test duration1 min
High energy surge voltages (SURGE), In-
stallation Class III
IEC 60255-22-5, IEC 61000-4-5
Impulse: 1,2
μ
s/50
μ
s
Auxiliary voltage
common mode: 4 kV; 12
Ω
; 9
μ
F
diff. mode:1 kV; 2
Ω
; 18
μ
F
relay outputs
common mode: 4 kV; 42
Ω
; 0,5
μ
F
communication
common mode: 4 kV; 12
Ω
; 9
μ
F
HF on lines, amplitude-modulated,
Class III
IEC 60255-22-6, IEC 61000-4-6
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
Power system frequency magnetic field
IEC 61000-4-8, Class IV;
30 A/m continious; 300 A/m for 3 s