7XV5662-0AA00/GG
English
C53000-B1174-C134-8
51
Interfaces to a communication device
Electrical Tests
Insulation Test
Isolation coordination according to IEC / EN / UL 60950-1 overvoltage category II, pollution
degree 2.
Isolation coordination according to IEC / EN 60255-27 overvoltage category III, pollution
degree 2.
X.21
Terminal
15-pole DSUB plug, potential-free
Transmission rate, synchron
64 kBit/s, 128 kBit/s, 256 kBit/s or 512 kBit/s
Transmission rate, asynchron
max.115,2 kBaud at 512 kbit/s
(see chapter Features)
Cable
see chapter Connection Instructions,
Installation and Commissioning
G.703.1
Terminal
9-pole DSUB socket, potential-free
Transmission rate, synchron
64 kBit/s
Transmission rate, asynchron
0,3 kBaud at 19,2 kBaud
Cable
see chapter Connection Instructions,
Installation and Commissioning
Regulations
IEC 60950-1
for more standards see also individual
functions
In-/outputs
Insulation
Voltage range
test voltage
Impulse vol-
tage
auxiliary voltage
double insulation
300 V
3,51 kV
5 kV
relais contact
couble insulation
300 V
3,51 kV
5 kV
G.703.1
Basic insulation
< 10 V
1,5 kV
1 kV
X.21
Basic insulation
< 10V
1,5 kV
1 kV