English
7XV5662-0AA00/GG
34
C53000-B1174-C134-8
Return damaged devices to the manufacturer, stating the defect. Use the original
packaging or transport packaging that meets the requirements of standard ISO 2248.
Repacking a Device
If you store devices after incoming inspection, pack them in suitable storage packaging.
If devices are to be transported, pack them in transport packing.
Put the accessories supplied and the test certificate in the packing with the device.
Before initial energization with supply voltage, or after storage, the relay shall be situated in
the operating area for at least two hours in order to ensure temperature equalization and to
avoid humidity influences and condensation.
Storing a Device
Only store devices on which you have carried out an incoming inspection, thus ensuring
that the warranty remains valid. The incoming inspection is described in the Operating
manual.
SIPROTEC devices must be stored in rooms, which are clean and dry. Devices or
associated replacement modules must be stored at a temperature of -40 °C to +85 °C
(-40 °F to 185 °F).
The relative humidity must be at a level where condensate and ice is prevented from
forming.
Siemens recommends that you observe a restricted storage temperature range of +10 °C
to +35 °C (50 °F to 95 °F), in order to prevent the electrolytic capacitors used in the power
supply from aging prematurely.
If the device has been in storage for more than 2 years, connect it to an auxiliary voltage
for 1 to 2 days. This will cause the electrolytic capacitors to form on the printed circuit
board assemblies again.
Transport
If devices are to be shipped elsewhere, you can reuse their transport packaging. If using
other packaging, ensure that the transport requirements according to ISO 2248 are met.
Storage packaging for individual devices is not adequate for transport purposes.