7SG1641 Ohmega 402 60 Relay Settings
©2013 Siemens Protection Devices Limited
Chapter 4 Page 3 of 20
1 Menu Settings
System Configuration Menu
Setting
Range
Default
Active Group
1, 2 … 8
1
CVT in use
YES, NO
NO
CT Ratio
0, 100, … 5000: 1,2,5
2000:1
VT Ratio
1000, 1100, … 10000, 11000, … 600000:
90, 95, … 130
132000:110
Alternate Setting Group
1, 2 … 8
1
View/Edit Group
1, 2 … 8
1
Default Screens Timer
Off..60
60
Date
1/ 1/1980
Time
00:00:00
Backlight timer
Off..60
5
Change Password
AAAA … ZZZZ
NOT ACTIVE
Relay Identifier
Up to 16 characters
OHMEGA 402-60
Distance Protection Menu
Setting
Range
Default
Active Scheme
Time Stepped, PUR, POR1, POR2, BOR
Time Stepped
CT Secondary
1, 2, 5
1A
Line Angle
0, 5, … 90 Deg
75 Deg
EF Comp Z0/Z1 ratio
0, 0.01, … 10.00
2.50
EF Comp Z0 angle
0, 5, … 355 Deg
75 Deg
POR Weak Infeed
Enabled, Disabled
Enabled
WI Local Trip
Enabled, Disabled
Enabled
WI Voltage Level
5, 5.5, …85 v
54.0 v
Z1 Phase Fault
Enabled, Disabled
Enabled
Z1 PF Impedance
0.5, 0.51, … 10.0,
10.1, 10.2, … 100,
101, … 250
8.00 Ohm
Z1 PF Time Delay
0, 10, … 10000ms
0ms
Z1 Earth Fault
Enabled, Disabled
Enabled
Z1 EF Impedance
0.5, 0.51, … 10.0,
10.1, 10.2, … 100,
101, … 250
8.00 Ohm
Z1 EF Time Delay
0, 10, … 10000ms
0ms
Z2 Phase Fault
Enabled, Disabled
Enabled
Z2 PF Impedance
0.5, 0.51, … 10.0,
10.1, 10.2, … 100,
101, … 250
16.00 Ohm
Z2 PF Time Delay
0, 10, … 10000ms
1000ms
Z2 Earth Fault
Enabled, Disabled
Enabled
Z2 EF Impedance
0.5, 0.51, … 10.0,
10.1, 10.2, … 100,
101, … 250
16.00 Ohm
Z2 EF Time Delay
0, 10, … 10000ms
1000ms
Z3 Phase Fault
Enabled, Disabled
Enabled
Z3 PF Type
Fwd Mho, Rev Mho, Offset Mho, Offset
Shaped
Offset Mho
Z3 PF Impedance (Fwd)
0.5, 0.51, … 10.0,
10.1, 10.2, … 100,
101, … 250
24.00 Ohm
Z3 PF Impedance (Rev)
0.5, 0.51, … 10.0,
10.1, 10.2, … 100,
101, … 250
8.00 Ohm
Z3 PF Shape Factor 1
0, 0.01, … 1.00
1.00