7SG15 MicroTAPP Description of Operation
©2013 Siemens Protection Devices Limited
Chapter 1 Page 32 of 38
Remote Raise
Initiate manual Tap Raise operation - Relay must be in Manual and
Remote modes.
Remote Lower
Initiate manual Tap Lower operation - Relay must be in Manual and
Remote modes.
Remote Auto
Switch to Auto operation – Relay must be in Remote mode.
Remote Manual
Switch to Manual operation – Relay must be in Remote mode.
Select Auxiliary Target 1
Change Target Voltage. Available when the Relay is both in Local and
Remote modes. Only one Auxiliary Target can be active at a time. If
more than one input is raised, the highest numbered input (1, 2 or 3)
takes priority.
Select Auxiliary Target 2
Change Target Voltage. Available when the Relay is both in Local and
Remote modes. Only one Auxiliary Target can be active at a time. If
more than one input is raised, the highest numbered input (1, 2 or 3)
takes priority.
Select Auxiliary Target 3
Change Target Voltage. Available when the Relay is both in Local and
Remote modes. Only one Auxiliary Target can be active at a time. If
more than one input is raised, the highest numbered input (1, 2 or 3)
takes priority.
Local / Remote
Select Local (input low) or Remote (input high) mode. This will only
have an effect if setting "Local / Remote Control" is set to "Status Input".
[102] Voltage Target Increase
Step increase Target Voltage. To maximum of +20%.
[102] Voltage Target Decrease
Step decrease Target Voltage. To maximum of -20%.
[102] Voltage Target Reset
Reset Target Voltage level.
Select Group 1
Temporarily switch Active Settings Group to Group 1.
Select Group 2
Temporarily switch Active Settings Group to Group 2.
Select Group 3
Temporarily switch Active Settings Group to Group 3.
Select Group 4
Temporarily switch Active Settings Group to Group 4.
Select Group 5
Temporarily switch Active Settings Group to Group 5.
Select Group 6
Temporarily switch Active Settings Group to Group 6.
Select Group 7
Temporarily switch Active Settings Group to Group 7.
Select Group 8
Temporarily switch Active Settings Group to Group 8.
As for outputs, any functional input can be allocated to any status input.
Communication Interface
Station Address
Sets Relay address for communications.
IEC870 on Port
Selects the port to be used.
COM 1 Baud Rate
Selects transmission speed.
COM 1 Parity
Determines whether or not a parity check is transmitted with communication
data.
COM 1 Line Idle
Sets the communication line idle sense.
COM 1 Data Echo
Enables connection of relays in a Ring.
COM 2 Baud Rate
Selects transmission speed.
COM 2 Parity
Determines whether or not a parity check is transmitted with communication
data.
COM 2 Line Idle
Sets the communication line idle sense.
COM 2 Data Echo
Enables connection of relays in a Ring.
COM 2 Direction
Configures COM 2 to use Relay Front or Rear port, or to Auto-Detect which
is active.
IEC60870 Class 2
Refresh Rate
Interval between creation of new IEC60870 class 2 measurand data
frames.
IEC60870 Class 2
Window
Percentage of nominal figures which must be exceeded for new IEC60870
class 2 measurand data frame to be created.
Data Storage
Clear All Events
Clears all Event records
Clear All Faults
Clears all Fault records
Tap-Changer Maintenance
Delta Count Alarm
Number of Tap-Changer operations before an Alarm is given.
Sum I
2
Alarm
Accumulated I
2
level which must be exceeded before Alarm is given.