5.4
Direct burial
Recommendations for direct burial of remote sensor:
● Check for visible damages in paint finish !
● Use protection conduit !
● Protect sensor with pea gravel at least 300 mm around sensor. This provides some
drainage and also avoids caking sensor with earth. It also helps to locate sensor in case
excavation takes place.
Figure 5-2
Direct burial of sensor
CAUTION
Sensor should not be subject to heavy vehicles applying excessive weight above sensor
or pipeline
NOTICE
SENSORPROM
memory unit
Remove the SENSORPROM from terminal box on sensor and relocate in remote
transmitter prior to burying sensor.
All sensor data plate information and serial number should be recorded for each sensor
prior to burying. This will ensure correct matching with SENSORPROM unit.
WARNING
Electrical cable identification
Use suitable coil and electrode cables
Lay electrical cable identification tape above pea gravel before it is covered with earth.
Connecting
5.4 Direct burial
SITRANS FM MAG 5100 W
Operating Instructions, 01/2020, A5E03063678-AC
39
Содержание 7ME652
Страница 6: ...Table of contents SITRANS FM MAG 5100 W 6 Operating Instructions 01 2020 A5E03063678 AC ...
Страница 10: ...Introduction 1 9 Notes on warranty SITRANS FM MAG 5100 W 10 Operating Instructions 01 2020 A5E03063678 AC ...
Страница 22: ...Description 3 3 Theory of operation SITRANS FM MAG 5100 W 22 Operating Instructions 01 2020 A5E03063678 AC ...
Страница 40: ...Connecting 5 4 Direct burial SITRANS FM MAG 5100 W 40 Operating Instructions 01 2020 A5E03063678 AC ...
Страница 46: ...Service and maintenance 6 7 Disposal SITRANS FM MAG 5100 W 46 Operating Instructions 01 2020 A5E03063678 AC ...