Temperatures, pressures, flow, limits
D
D
** 30 Display, enter actual temperature and setpoint
temperature of oven
3
Enter setpoint
temperature
CL
0
The temperatures of the sample gas probe are
in ˚C. The minimum value is 110 ˚C, the maxi-
mum value 200 ˚C.
The actual temperature is initially displayed for
approx. 3 s, and then the setpoint temperature.
Factory setting: 190
** 33 Display, enter actual temperature and setpoint
temperature of sample gas probe
3
Enter setpoint
temperature
CL
3
Display
actual
temp.
The temperatures of the oven are in ˚C. The
minimum value is 110 ˚C, the maximum value
200 ˚C.
The actual temperature is initially displayed for
approx. 3 s, and then the setpoint temperature.
Factory setting: 200
** 30 Display, enter actual temperature and setpoint
temperature of oven
3
Enter setpoint
temperature
CL
0
Display
actual
temp.
The temperatures of the pump are in ˚C. The
minimum value is 110 ˚C, the maximum value
190 ˚C.
The actual temperature is initially displayed for
approx. 3 s, and then the setpoint temperature.
Factory setting: 190
** 31 Display, enter actual temperature and setpoint
temperature of pump
3
Enter setpoint
temperature
CL
1
Display
actual
temp.
The temperatures of the heated line are in ˚C.
The minimum value is 110 ˚C, the maximum
value 200 ˚C.
The actual temperature is initially displayed for
approx. 3 s, and then the setpoint temperature.
Factory setting: 190
** 32 Display, enter actual temperature and setpoint
temperature of heated line
3
Enter setpoint
temperature
CL
2
Display
actual
temp.
A-21