Building Technologies
74 319 0618 0 a
17.04.2008
59/276
en
173 Amplification
of
locking signal
100 %
(0…200)
....................
%
Response to locking signals
174 Pump overrun time
6 min
(0…40)
................
min
175 Periodic pump run
(pump kick)
0
(0 / 1)
.........................
0 = no periodic pump run
1 = weekly pump run activated
176 Winter- / summer-
time changeover
25.03
(01.01. … 31.12)
Setting: Earliest possible change-
over date
177 Summer- / winter-
time changeover
25.10
(01.01. … 31.12)
Setting: Earliest possible change-
over date
178 Clock operation
0
(0…3)
.........................
0 = autonomous clock in the
controller
1 = clock from bus (slave), with no
remote setting
2 = clock from bus (slave), with
remote setting
3 = controller is the central clock
(master)
179 Bus power supply
A
(0 / A)
.........................
0 = no bus power supply through
the controller
A = bus power supply through the
controller
180 Outside
tempera-
ture source
A
(A / 00.01…14.16)
.........................
No display means: Controller is
autonomous (no data bus pre-
sent).
Setting when supplied via the data
bus: segment and device number
of source,
or
A for automatic
identification of source
181 Heat demand output
Ux DC 0…10 V
130 °C
(30…130)
...................
°C
Scaling for DC 10 V
194 Hours run counter
Display function
Number of controller operating
hours
195 Controller's soft-
ware version
Display function