The Circuit-breaker function block activates the device contact and thus causes the circuit breaker to open
(see
). The command output time is also effective here. In the trip logic, the decision is made
whether to trigger 1-pole tripping or not (3-pole coupling) (see
The trip logic also decides when the protection trip command is terminated (see
).
[loausl1p-070211-01.tif, 1, en_US]
Figure 5-34
1-Pole or 3-Pole Operate and 3-Pole Coupling
1-Pole or 3-Pole Operate
Under certain circumstances, the device can cause 1-pole operate in the event of 1-phase or 2-phase faults.
The device always causes 3-pole operate in the event of 3-phase short circuits.
The preconditions for 1-pole operate are:
•
The device is designed for 1-pole operate (see Order reference).
•
The tripping protection function can generate 1-pole operate indications and is set accordingly (
1-pole
operate allowed
parameter set to
yes
).
•
The circuit-breaker function group allows 1-pole operate.
To do this, set the
1-pole operate allowed
parameter in the circuit-breaker function group (see
General parameters of the function group) to
yes
.
•
The Automatic reclosing function is active and generates the
79 permits 1-pole trip
signal. The
function thus indicates that it is healthy for 1-pole reclosing after 1-pole operate.
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual
231
C53000-G5040-C015-9, Edition 11.2017
Содержание 6MD85
Страница 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Страница 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...