Installation and removal
4.3 Wall mounting
SCALANCE S615
Operating Instructions, 10/2022, C79000-G8976-C389-07
37
4.3
Wall mounting
Note
The wall mounting must be capable of supporting four times the weight of the device, but at
least 50 N. For information on the weight, refer to the section "Technical specifications
(Page 63)".
Installation
1.
Prepare the drill holes for wall mounting. For the precise dimensions, refer to the section
"SCALANCE S615 (Page 68)".
2.
Secure the device to the wall with two screws. When mounting on a wall, use mounting
fittings suitable for the type of wall.
3.
Connect the power supply, refer to the section "Power supply (Page 51)".
4.
Fit the connectors for the digital input and digital output, refer to the section "Digital
input/output (Page 53)".
5.
Connect the device to the local network, refer to the section "Ethernet port (Page 55)".
6.
Connect the terminal with as
short a cable as possible ≤ 150 mm and a large cross
-sectional
area of 1.5 mm² to the functional ground of the system, see section "Terminals (Page 25)“
and section “Grounding (Page 52)“.