Parameters/address space
4.1 Parameters
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
18
Manual, 03/2019, A5E45488510-AA
Table 4- 2
Port parameter (GSD file)
Parameters
Value range
Default
Port configuration
Operating mode
•
IO-Link Autostart
•
IO-Link Manual
•
DI
•
Deactivated
IO-Link Autostart
Length of the input data*
depending on the selected in-
put/output type**
depending on the selected in-
put/output type**
Length of output data
depending on the selected in-
put/output type**
depending on the selected in-
put/output type**
Vendor ID***
Manufacturer ID of the connected
IO-Link device
0
Device ID***
Device ID of the connected IO-
Link device
0
Inspection Level/Data Stor-
age***
•
Identical type (V1.0) without
Backup&Restore
•
Type-compatible (V1.1) with-
out Backup&Restore
•
Type-compatible (V1.1) with
Backup&Restore
•
Type-compatible (V1.1) with
Restore
Type-compatible (V1.1) with
Backup&Restore
* If PQI is activated, 1 byte less space remains for input data of the device. For example: GSD setting
16 bytes = 15 bytes + PQI
** Make sure not to exceed the maximum possible length of the input or output data for all ports.
*** Only effective if you use the "IO-Link Manual" port mode.
Maximum possible length of the input or output data
Example:
You have selected the configuration 64I/64Q.
You have assigned 4 bytes of input data to the first port.
For the remaining ports, you can assign a total of 60 bytes of input data.
Reference
You can find additional information on the Vendor ID and Device ID on the Internet
https://support.industry.siemens.com/cs/ww/en/view/109748852