Functions
3.3 Identification data
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
32
Manual, 02/2010, A5E01075965-03
Reading of identification data
Table 3- 9
Identification data
Identification data
Access
Default setting
Description
Identification data 0: Index 1 (Data record 231)
MANUFACTURER_ID
read (2 Byte)
2A hex (= 42 dec)
The name of the manufacturer is stored
here. (42 dec = SIEMENS AG)
ORDER_ID
Read (20 bytes)
Depends on the
module
Order number of the module
SERIAL_NUMBER
Read (16 bytes)
Not relevant
HARDWARE_REVISION
read (2 Byte)
Not relevant
SOFTWARE_REVISION
Read (4 bytes)
Firmware version
This indicates the firmware version of the
module.
REVISION_COUNTER
read (2 Byte)
-
Provides information on parameter
modifications on the module.
PROFILE_ID
read (2 Byte)
F600 hex
Generic Device
PROFILE_SPECIFIC_TYPE
read (2 Byte)
0003 hex
0005 hex
On electronic modules
on interface modules
IM_VERSION
read (2 Byte)
0101 hex
Provides information on the ID data version
(0101 hex = version 1.1)
IM_SUPPORTED
read (2 Byte)
000E hex
Provides information on existing
identification data (index 2 to 4)
Maintenance data 1: Index 2 (Data record 232)
TAG_FUNCTION
Read/write (32
bytes)
-
Define a unique identifier for the module in
this record.
TAG_LOCATION
Read/write (22
bytes)
-
Enter the installation location of the module
here.
Maintenance data 2: Index 3 (data record 233)
INSTALLATION_DATE
Read/write (16
bytes)
-
Enter the installation date of the module
here.
RESERVED
Read/write (38
bytes)
-
Reserved
Maintenance data 3: Index 4 (data record 234)
DESCRIPTOR
Read/write (54
bytes)
-
Enter a comment on the module here.