Error and system messages
4.1 LED displays on the interface module
IM151-1 FO STANDARD interface module (6ES7151-1AB05-0AB0)
Manual, 02/2010, A5E01075965-03
37
The following errors can only occur if you have configured the ET 200S at a master from a
different supplier or by using the GSD file:
Error type
(BF)
Error location,
error code
(SF/BF)
Cause
Remedy
01
Configuration error at the option
handling
Option handling has been configured
but no power module was configured
for options handling.
4
02 to 63 (slot) Option handling has been configured
but more than one power module was
configured for options handling. The
slot of the second power module that
has option handling is displayed.
Change the configuration.
01
General parameter assignment error
The number of module parameter
blocks in the parameter assignment
telegram does not agree with the
number of identifiers in the
configuration telegram.
02
The maximum address area (inputs
and outputs) of the interface module
has been exceeded.
5
1
03
Incorrect structure of the parameter
assignment telegram.
Correct the configuration.
1
You prevent this error when configuration is carried out with STEP 7 and it is only possible if other
configuration tools are used.
See also
Incorrect module configurations of ET 200S on the PROFIBUS DP (Page 55)
Service & su