Technical specifications
5.6 Ambient conditions
IFP2200 INOX MT ETH
Compact Operating Instructions, 07/2021, A5E42185570-AD
41
Climatic ambient conditions
The following table shows the climatic ambient conditions for operation of the device.
Ambient conditions
Permitted range
Comments
Temperature
•
Vertical mounting
0 ... 45 °C (landscape format)
0 ... 40 °C (portrait format)
•
Mounting at an angle
0 ... 40 °C (landscape format)
0 ... 35 °C (portrait format)
Slope angle max. 35°
Relative humidity
10 ... 90 %, no condensation at
the rear of the device
Atmospheric pressure,
operation elevation
1140 to 795 hPa
Corresponds to an elevation
of -1000 to 2000 m
Pollutant concentration
In accordance with ANSI/ISA-71.04-2013 severity level G3
Note the information in section "Safety instructions and further information (Page 10)" and
the information on the mounting positions:
•
Permitted mounting positions of the built-in units (Page 17)
5.6.3
Electromagnetic compatibility
Pulse-shaped interference
The following table shows the electromagnetic compatibility of modules with regard to pulse-
shaped interference. This requires the device to meet the specifications and directives for
electrical installation.
Pulse-shaped interference
Test voltage
Degree of se-
verity
Electrostatic discharge
in accordance with IEC 61000-4-2
Air discharge: 8 kV
3
Contact discharge: 6 kV (front)
Contact discharge: 4 kV (rear)
2
Bursts
(high-speed transient interference)
in accordance with IEC 61000-4-4
2 kV power supply cable
2 kV signal cable, > 30 m
1 kV signal cable, < 30 m
3
Powerful single pulse (surge) according to IEC 61000-4-5, external protective circuit is required (see
function manual "SIMATIC S7-1500, ET 200MP, ET 200SP, ET 200AL Designing interference-free con-
trollers", section 7 "Lightning protection and overvoltage protection") on the Internet
https://support.industry.siemens.com/cs/ww/en/view/59193566
Asymmetrical coupling
2 kV power supply cable
DC voltage with protective elements
1
2 kV signal/data cable, > 30 m,
with protective elements as required
1
3
Symmetrical coupling
1 kV power supply cable
DC voltage with protective elements
1
1 kV signal cable, > 30 m,
with protective elements as required
1
3
1
The following lightning protection element was used during the testing of the Industrial Flat Panel:
Dehn BVT AVD 24" (Order No. 918 422)